| 2016-04-22 12:17:57 | FAILED 2ND ELECTRICAL REVIEW |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011 |
| | EDITION |
| | |
| | CORRECTIONS REQUIRED: |
| | AS INSTRUCTED IN THE EMAIL ENCLOSED WITH THE SUBMITTAL |
| | YOU TOLD TO PROVIDE A SITE PLAN INDICATING THE LOCATION |
| | OF THE SERVICE EQUIPMENT ON THE PROPERTY. YOU WERE |
| | INSTRUCTED TO SUBMIT PROPER LOAD CALCS WHICH ARE A PART |
| | OF THE FEEDER DIAGRAM AS MENTIONED ON NEC 215.5. |
| | LOOKING AT THE PROPERTY RECORDS, THERE APPEARS TO BE |
| | TWO BLDGS. ON THE PROPERTY REMEMBER THAT THE NEC |
| | REQUIRES THAT ALL DISCONNECTS BE GROUPED TOGETHER. |
| | FURTHERMORE, UNLESS THERE IS A COMMON LAUNDRY FACILITY |
| | THERE SHALL BE A LAUNDRY CIRCUIT CALCULATED INTO THE |
| | LOAD OF EACH UNIT. THE SAME HOLDS TRUE FOR THE |
| | EMERGENCY LIGHTING REQUIRED FOR THE STAIRS. YOU WERE |
| | ALSO ASKED TO INCLUDE THE SCOPE OF WORK ON THE |
| | DRAWINGS. THE RISER DIAGRAM MEANS NOTHING WITHOUT KNOW |
| | WHAT IT IS MEANT FOR. YOU DID INCLUDE THE JOB ADDRESS |
| | AND THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE |
| | FOR THE DESIGN. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |