| 2016-04-28 14:57:52 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16030649 | | | 3/22/16 | | | | | | COMMENTS FROM THE 1ST REVIEW STILL EXIST. PLEASE NOTE | | | THAT THE SUBMITTED HEAT LOAD CALCULATIONS ARE NOT | | | VENTILATION CALCULATIONS- SEE COMMENT #2 | | | | | | 1) SHOW THE LOCATIONS OF THE RETURN GRILLS IN THE DOORS | | | AND INDICATE THEIR SIZES AND CFM CAPACITIES (PLEASE | | | REVIEW THE PERMIT APPLICATION- RETURN GRILLS IN THE | | | INTERIOR DOORS IS LISTED IN THE WORK DESCRIPTION). | | | 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | OCCUPIED ROOMS AND SPACES OF THE PROPOSED OCCUPANCY IN | | | COMPLIANCE WITH SECTION 809.2 FBC-14 EXISTING BUILDING | | | AND TABLE 403.3 FBC-14 MECHANICAL. PROVIDE A SCHEDULE | | | INDICATING THE REQUIRED AND PROVIDED CFM'S OF OUTDOOR | | | AIR. | | | 3) PLEASE PROVIDE A SCOPE OF WORK FOR MECHANICAL ON THE | | | PLANS WITH CORREPONDING DRAWINGS AND DETAILS ( THE | | | REMOVED DROP CEILING AND NEW ROOM LAYOUTS- AS NOTED IN | | | THE PERMIT APPLICATION WORK DESCRIPTION- WILL MOST | | | LIKELY AFFECT THE EXISTING HVAC SYSTEM). | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|