2016-04-28 14:57:522ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030649
 3/22/16
  
 COMMENTS FROM THE 1ST REVIEW STILL EXIST. PLEASE NOTE
 THAT THE SUBMITTED HEAT LOAD CALCULATIONS ARE NOT
 VENTILATION CALCULATIONS- SEE COMMENT #2
  
 1) SHOW THE LOCATIONS OF THE RETURN GRILLS IN THE DOORS
 AND INDICATE THEIR SIZES AND CFM CAPACITIES (PLEASE
 REVIEW THE PERMIT APPLICATION- RETURN GRILLS IN THE
 INTERIOR DOORS IS LISTED IN THE WORK DESCRIPTION).
 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 OCCUPIED ROOMS AND SPACES OF THE PROPOSED OCCUPANCY IN
 COMPLIANCE WITH SECTION 809.2 FBC-14 EXISTING BUILDING
 AND TABLE 403.3 FBC-14 MECHANICAL. PROVIDE A SCHEDULE
 INDICATING THE REQUIRED AND PROVIDED CFM'S OF OUTDOOR
 AIR.
 3) PLEASE PROVIDE A SCOPE OF WORK FOR MECHANICAL ON THE
 PLANS WITH CORREPONDING DRAWINGS AND DETAILS ( THE
 REMOVED DROP CEILING AND NEW ROOM LAYOUTS- AS NOTED IN
 THE PERMIT APPLICATION WORK DESCRIPTION- WILL MOST
 LIKELY AFFECT THE EXISTING HVAC SYSTEM).
  