  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. (
 ADDRESSING RESPONSES 2ND REQUEST )
  
 - THE SCOPE OF WORK IS AN ALTERATION LEVEL 2 THEREFORE
 EMERGENCY & EXIT LIGHTING SHALL BE PROVIDED IN THE
 ELECTRICAL ROOM. FBC-B1006.2, FBC-B1011. SHOW
 ILLUMINATION BY THE ELECTRICAL SERVICE AND PANEL BOARD
 EQUIPMENT NEC 110.26(D).
 - NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED
 BY LIGHTING CIRCUIT OF SAME LOCAL AREA. MAKE A GENERAL
 NOTE SINCE NOT INDICATED ON THE FLOOR PLANS.
 - ON THE RISER DIAGRAMS SHOWS DEMO OF EXISTING PANELS
 AND CONDUITS FROM PANEL ?A? THEREFORE SEALING THESE
 UNUSED OPENINGS WILL BE REQUIRED IN ACCORDANCE WITH NEC
 110.12. PANEL SCHEDULE IS MISSING AIC AND SCR OF
 ELECTRICAL APPARATUS NEC 110.9, 110.10. ARC-FLASH
 HAZARD WARNING LABELS & AVAILABLE FAULT CURRENT
 MARKINGS NEC 110.16, 110.24.
 - AGAIN IF NEW LIGHTING IS BEING INSTALLED MINIMUM
 ENERGY CODE REQUIREMENTS SUCH AS MANDATORY LIGHTING
 CONTROLS WILL APPLY. FBC-E C405.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  