| 2016-05-07 10:54:09 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030649 |
| | ADD: 6620 S. DIXIE HWY. |
| | CONT: JORGE E. HERNANDEZ |
| | TEL: 954-678-7580 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SAT. MAY07/ 2016 |
| | ACTION: DENIED |
| | |
| | |
| | |
| | 1-2) COMPLIED. |
| | |
| | 3) 2ND REQUEST. THE ENGINEER OF RECORD DOES INDICATE |
| | THE 3 PRODUCT APPROVALS THAT HE HAS APPROVED BUT THE 3 |
| | PRODUCT APPROVALS WERE NOT SUBMITTED BY THE CONTRACTOR. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(B) WINDOWS |
| | |
| | 4) 2ND REQUEST. THE ENGINEER OF RECORD DOES INDICATE |
| | THE 3 PRODUCT APPROVALS THAT HE HAS APPROVED BUT THE 3 |
| | PRODUCT APPROVALS WERE NOT SUBMITTED BY THE CONTRACTOR. |
| | 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5-6) COMPLIED. |
| | |
| | 7) SEMI-COMPLIED. IN THE 2ND ROUND OF REVIEWS THE DOOR |
| | SIZES ARE PROVIDED. THE DOOR LEADING TO THE LADIES |
| | RESTROOM IS LABELED A 2'-8" DOOR. PLEASE PROVIDE |
| | CONFORMANCE WITH THE 2014 FBC-ACCESSIBLITY CODE, |
| | SECTION 404.2.3 CLEAR WIDTH. DOOR OPENINGS SHALL |
| | PROVIDE A CLEAR WIDTH OF 32 INCHES (815 MM) MINIMUM. |
| | CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE |
| | MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, |
| | WITH THE DOOR OPEN 90 DEGREES. |
| | |
| | 2014 FBC-ACCESS. CODE 202.4.1 202.4.1 DISPROPORTIONATE |
| | COST. WILL REQUIRE THE CONTRACTOR TO SPEND UP TO AN |
| | ADDITIONAL $1150.00 DOLLARS IN ACCESSIBLE UPGRADES. |
| | THIS AMOUNT OF FUNDS SHOULD ALLOW FOR THE LARGER DOOR |
| | SIZE. |
| | 2014 FBC-ACCESS. CODE 202.4.1 202.4.1 DISPROPORTIONATE |
| | COST. |
| | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |