| Plan Review Notes For Permit 16030649 |
| Permit Number |
16030649 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-22 07:16:09 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16030649 | | | 3/22/16 | | | | | | 1) SHOW THE LOCATIONS OF THE RETURN GRILLS IN THE DOORS | | | AND INDICATE THEIR SIZES AND CFM CAPACITIES. | | | 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | OCCUPIED ROOMS AND SPACES OF THE PROPOSED OCCUPANCY IN | | | COMPLIANCE WITH SECTION 809.2 FBC-14 EXISTING BUILDING | | | AND TABLE 403.3 FBC-14 MECHANICAL. PROVIDE A SCHEDULE | | | INDICATING THE REQUIRED AND PROVIDED CFM'S OF OUTDOOR | | | AIR. | | | 3) PLEASE PROVIDE A SCOPE OF WORK FOR MECHANICAL ON THE | | | PLANS WITH CORREPONDING DRAWINGS AND DETAILS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|