Plan Review Notes
Plan Review Notes For Permit 16030649
Permit Number 16030649
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-16 10:39:30JOB PERMIT NUMBER: 16030649
 JOB ADDRESS: 6620 S DIXIE HIGHWAY
 WEST PALM BEACH FLORIDA
 DATE: MARCH 16 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - MISSING EMERGENCY LIGHTING & EXIT SIGNAGE BY DOUBLE
 DOOR ON THE WEST SIDE OF BUILDING AND INTERIOR OF
 ELECTRICAL ROOM. FBC-B1006.2 , FBC-B1011
 - NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED
 BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE
 LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON
 OWN CIRCUIT.
 - NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, PANELBOARDS.
 - PROVIDE A NOTE STATING ALL UNUSED OPENINGS ON
 ELECTRICAL PANELBOARD CABINET A WILL BE ADEQUATELY
 SEALED SINCE DEMO OF PANEL EQUIPMENT B & C. NEC 110.12
 A
 - PROVIDE AIC RATING OF ELECTRICAL APPARATUS ALONG WITH
 EXISTING LOAD CALCULATIONS AND SERVICE / FEEDER
 CONDUCTOR / CONDUIT SIZES. NEC 215.5 , ARC-FLASH HAZARD
 WARNING LABEL & AVAILABLE FAULT CURRENT MARKING IS
 REQUIRED. NEC 110.16 , 110.24
 - IF NEW LIGHTING IS BEING INSTALLED MINIMUM ENERGY
 CODE REQUIREMENTS SUCH AS MANDATORY LIGHTING CONTROLS
 WILL APPLY ? PLEASE CLARIFY ? FBC-E C405
  
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  