| 2016-03-22 07:57:02 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030649 |
| | ADD: 6620 S. DIXIE HWY. |
| | CONT: JORGE E. HERNANDEZ |
| | TEL: 954-678-7580 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. MARCH 21/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) THE RESIDENTIAL DESIGNER ERVIN KEEL CANNOT HAVE |
| | THEIR NAME ADDRESS, TELEPHONE NUMBER NOR E-MAIL ADDRESS |
| | ON THESE PLANS SINCE THEY ARE NOT LICENSED FOR |
| | COMMERCIAL WORK, THIS IS CONSIDERED ADVERTISING. |
| | 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED |
| | BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE: |
| | NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR, |
| | THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE |
| | NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER |
| | OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER |
| | IS PRACTICING (471.025 F.S. AND 471.023 F.S.). |
| | |
| | 2) THE PLANS INDICATE A TOTAL OF 6 NEW WINDOWS 4 ON THE |
| | SOUTH ELEVATION AND 2 ON THE WEST ELEVATION. THE PLANS |
| | INDICATE THE USE OF # 5 REBARS VERTICALLY IN THE |
| | ADJACENT BLOCK CELLS OF THE WINDOW BUT THE PLANS DO NOT |
| | INDICATE HOW THE REBAR IS GOING TO BE ATTACHED INTO THE |
| | BEAM OR THE MONOLITHIC SLAB NOR DOES THE PLAN INDICATE |
| | THE MINIMUM LAP FOR THE REBARS. 2014 FBC-B 2107.2.1. |
| | |
| | 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(B) WINDOWS |
| | |
| | 4) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5) THE DESIGNER HAS DESIGNED THE WIND DESIGN EXPOSURE |
| | TO A HIGHER EXPOSURE D WITH HIGHER PRESSURES ASSOCIATED |
| | WITH THIS EXPOSURE. WE WILL REVIEW TO THE DESIGNERS |
| | HIGHER PRESSURES AS EXPRESSED IN THE DESIGN. THE |
| | UNKNOWN IS IF THE -65/+60 IS VULT OR VASD, NOT GIVEN? |
| | 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 6) THE PLANS INDICATE ON THE SOUTH SIDE OF THE BUILDING |
| | 1 WINDOW IS TO BE BLOCKED IN. THE PLANS DO NOT INDICATE |
| | THE USE OF ANY HORIZONTAL LADDER TYPE WALL |
| | RE-INFORCEMENT. FBC-B 2107.1/ ACI 530 12.7.4 JOINT |
| | RE-INFORCEMENT. |
| | |
| | 7) THE PLANS DO NOT INDICATE ON THE INTERIOR WHAT WALLS |
| | ARE EXISTING AND WHAT WALLS ARE NEW NOR DOES THE PLANS |
| | INDICATE ANY OF THE DOOR SIZES. 107.3.5.1.1 MINIMUM |
| | CRITERIA FOR COMMERCIAL PLAN REVIEW. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |