2016-03-22 07:57:02BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030649
 ADD: 6620 S. DIXIE HWY.
 CONT: JORGE E. HERNANDEZ
 TEL: 954-678-7580
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 21/ 2016
 ACTION: DENIED
  
 1) THE RESIDENTIAL DESIGNER ERVIN KEEL CANNOT HAVE
 THEIR NAME ADDRESS, TELEPHONE NUMBER NOR E-MAIL ADDRESS
 ON THESE PLANS SINCE THEY ARE NOT LICENSED FOR
 COMMERCIAL WORK, THIS IS CONSIDERED ADVERTISING.
 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 2) THE PLANS INDICATE A TOTAL OF 6 NEW WINDOWS 4 ON THE
 SOUTH ELEVATION AND 2 ON THE WEST ELEVATION. THE PLANS
 INDICATE THE USE OF # 5 REBARS VERTICALLY IN THE
 ADJACENT BLOCK CELLS OF THE WINDOW BUT THE PLANS DO NOT
 INDICATE HOW THE REBAR IS GOING TO BE ATTACHED INTO THE
 BEAM OR THE MONOLITHIC SLAB NOR DOES THE PLAN INDICATE
 THE MINIMUM LAP FOR THE REBARS. 2014 FBC-B 2107.2.1.
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
  
 4) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5) THE DESIGNER HAS DESIGNED THE WIND DESIGN EXPOSURE
 TO A HIGHER EXPOSURE D WITH HIGHER PRESSURES ASSOCIATED
 WITH THIS EXPOSURE. WE WILL REVIEW TO THE DESIGNERS
 HIGHER PRESSURES AS EXPRESSED IN THE DESIGN. THE
 UNKNOWN IS IF THE -65/+60 IS VULT OR VASD, NOT GIVEN?
 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 6) THE PLANS INDICATE ON THE SOUTH SIDE OF THE BUILDING
 1 WINDOW IS TO BE BLOCKED IN. THE PLANS DO NOT INDICATE
 THE USE OF ANY HORIZONTAL LADDER TYPE WALL
 RE-INFORCEMENT. FBC-B 2107.1/ ACI 530 12.7.4 JOINT
 RE-INFORCEMENT.
  
 7) THE PLANS DO NOT INDICATE ON THE INTERIOR WHAT WALLS
 ARE EXISTING AND WHAT WALLS ARE NEW NOR DOES THE PLANS
 INDICATE ANY OF THE DOOR SIZES. 107.3.5.1.1 MINIMUM
 CRITERIA FOR COMMERCIAL PLAN REVIEW.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT