Plan Review Notes
Plan Review Notes For Permit 16030552
Permit Number 16030552
Review Stop P
Sequence Number 4
Notes
Date Text
2016-08-30 10:19:41 
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PROVISO
 2014 FLORIDA ACCESSIBILITY CODE
 UNISEX BATHROOM
  
  
  
 1. THE OVERALL WIDTH OF ACCESSIBLE TOILET ROOMS SHOULD
 BE MIN OF 85IN MIN TO ACCOMMODATE THE 60 IN CLEARANCE
 OF THE TOILET AND THE SPACE NEEDED FOR THE LAV. WPB
 AMEND. TO FBC 107.2.1
  
 2. PLEASE SHOW CLEARANCE AROUND TOILETS TO COMPLY WITH.
 FBC ACC 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 3. PLEASE SHOW CLEAR FLOOR SPACE FOR LAVS. TO COMPLY
 WITH. FBC ACC 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED 305.3 SIZE.
 THE CLEAR FLOOR OR GROUND SPACE SHALL BE 30 INCHES (760
 MM) MINIMUM BY 48 INCHES (1220 MM) MINIMUM.
  
 4. ALL GRAB BARS SHALL BE MEASURED FROM THE FLOOR TO
 THE TOP OF THE GRIPING SURFACE. PER FBC ACC 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE
 HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A
 BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1.
  
 5. TOILET PAPER DISPENSER SHALL COMPLY WITHFBC ACC
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 6. THE BOTTOM OF THE MIRROR IS SHOWN AS 42IN OF
 FINISHED FLOOR IT SHALL BE 40IN MAX OF THE FLOOR. PER
 FBC ACC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTER SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 7. PLEASE SHOW GRAB BAR COMPLIANCE WITH FBC ACC 604.5.1
 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 8. THE CHILDREN'S TOILET COMPARTMENTS SHALL COMPLY WITH
 FBC ACC 604.9 WATER CLOSETS AND TOILET COMPARTMENTS FOR
 CHILDREN?S USE.
 WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S
 USE SHALL COMPLY WITH 604.9.
  
  
 ADVISORY 604.9 WATER CLOSETS AND TOILET COMPARTMENTS
 FOR CHILDREN?S USE.
 THE REQUIREMENTS IN 604.9 ARE TO BE FOLLOWED WHERE THE
 EXCEPTION FOR CHILDREN?S WATER CLOSETS IN 604.1 IS
 USED. THE FOLLOWING TABLE PROVIDES ADDITIONAL GUIDANCE
 IN APPLYING THE SPECIFICATIONS FOR WATER CLOSETS FOR
 CHILDREN ACCORDING TO THE AGE GROUP SERVED AND REFLECTS
 THE DIFFERENCES IN THE SIZE, STATURE, AND REACH RANGES
 OF CHILDREN AGES 3 THROUGH 12. THE SPECIFICATIONS
 CHOSEN SHOULD CORRESPOND TO THE AGE OF THE PRIMARY USER
 GROUP. THE SPECIFICATIONS OF ONE AGE GROUP SHOULD BE
 APPLIED CONSISTENTLY IN THE INSTALLATION OF A WATER
 CLOSET AND RELATED ELEMENTS.
  
  
  
 604.9.1 LOCATION.
 THE WATER CLOSET SHALL BE LOCATED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 12 INCHES (305 MM) MINIMUM
 AND 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 COMPARTMENTS SHALL BE ARRANGED FOR LEFT-HAND OR
 RIGHT-HAND APPROACH TO THE WATER CLOSET.
  
  
 ADVISORY SPECIFICATIONS FOR WATER CLOSETS SERVING
 CHILDREN AGES 3 THROUGH 12
  
 WATER CLOSET CENTERLINE 12 INCHES
 (305 MM) 12 TO 15 INCHES
 (
 TOILET SEAT HEIGHT 11 TO 12 INCHES
  
 GRAB BAR HEIGHT 18 TO 20 INCHES
  
 DISPENSER HEIGHT 14 INCHES
 (355 MM)
  
 9. SHT. S.2 DETAILS FOR DISABLE BATHS THE HEIGHT OF THE
 TOILET IS SHOWN AS 20IN ON ONE AND 18IN ON THE OTHER
 PLEASE CLARIFY. PER WPB AMEND. TO FBC 107.2.1
  
 11. S.2 THE TOILET LOCATION DOES NOT MATCH THE REST OF
 THE PLAN PLEASE CLARIFY. PER WPB AMEND. TO FBC 107.2.1
  
 12. THE NOTE ON SHT. P.2 FOR THE GREASE INTERCEPTOR IS
 INCORRECT A GREASE INTERCEPTOR IS REQUIRED IF YOU ARE
 SERVING FOOD WITH A GREASE. YOU WILL STILL BE WASHING
 UTENSILS AND SERVING TRAYS. PER FBC PL 1003.3.1 GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES
 REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL
 INCLUDE POT SINKS, PRETENSE SINKS; SOUP KETTLES OR
 SIMILAR DEVICES; WOK STATIONS; FLOOR DRAINS OR SINKS
 INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH
 UNITS AND DISHWASHERS WITHOUT PRETENSE SINKS. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED. WHERE LACK
 OF SPACE OR OTHER CONSTRAINTS PREVENT THE INSTALLATION
 OR REPLACEMENT OF A GREASE INTERCEPTOR, ONE OR MORE
 GREASE INTERCEPTORS SHALL BE PERMITTED TO BE INSTALLED
 ON OR ABOVE THE FLOOR AND UPSTREAM OF AN EXISTING
 GREASE INTERCEPTOR
  
  
 NEW COMMENTS:
  
 1. THE WATER CLOSET IN THE UNISEX BATHROOM AND THE BOYS
 BATHROOM ARE NOTED VENTED PROPERLY. PER FBC PL 910.1
 /912.1/915.1
  
 2. THE HOT WATER SYSTEM SHALL COMPLY WITH FBC PL 607.2
 HOT OR TEMPERED WATER SUPPLY TO FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 (15 240 MM). RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER.
 THE WAY YOU HAVE THE SYSTEM DESIGNED IT EXCEEDS THE 50
 FT IT CAN BE REDESIGNED SO THAT IT DOES NOT EXCEED
 50FT.
  
  
 PROVISO
 1. PROVIDE APPROVED CODE COMPLIANT ISOMETRIC DRAWING
 FOR FIRST ROUGH INSPECTION. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
 2. PROVIDE AN APPROVED SIGNED AND SEALED LETTER FROM
 DESIGNER OF RECORD FOR EXEMPTION OF GREASE INTERCEPTOR.
 PER WPB AMEND TO FBC 107.2.1
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved