| 2016-07-28 09:29:01 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | PASSED WITH THE FOLLOWING PROVISO | | | | | | - NEC 760.41(B) THE BRANCH CIRCUIT SUPPLYING FIRE ALARM | | | EQUIPMENT SHALL SUPPLY NO OTHER LOADS AND BE | | | PERMANENTLY MARKED IN RED AND IDENTIFIED AS: FIRE ALARM | | | CIRCUIT? AND BE ACCESSIBLE ONLY TO QUALIFIED PERSONNEL. |
|