2016-07-28 09:29:01REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO
  
 - NEC 760.41(B) THE BRANCH CIRCUIT SUPPLYING FIRE ALARM
 EQUIPMENT SHALL SUPPLY NO OTHER LOADS AND BE
 PERMANENTLY MARKED IN RED AND IDENTIFIED AS: FIRE ALARM
 CIRCUIT? AND BE ACCESSIBLE ONLY TO QUALIFIED PERSONNEL.