| 2016-08-01 07:00:15 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030552 |
| | ADD: 6901 OKEECHOBEE BLVD. |
| | CONT: RANDOLPH & DEWDNEY CONSTRUCTION |
| | TEL: 561-276-2889 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | DATE: WED. AUGUST 24/2016 |
| | ACTION: DENIED |
| | |
| | NEW DESIGNER OF RECORD, NEW DESIGN DOCUMENTS. 2ND |
| | REVIEW!!!! |
| | |
| | 1A) 2ND REVIEW. SHEET S.2 UNDER THE HEADING CODES FOR |
| | PROJECT LIST THIS AS A LEVEL II ALTERATION. PLEASE NOTE |
| | THIS PLAN REVIEW WILL BE UNDER THE 2014 FBC- EXISTING |
| | BUILDING CODE CHAPTER 10 CHANGE OF OCCUPANCY. 1001.3.1 |
| | PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION. WHERE A |
| | PORTION OF AN EXISTING BUILDING IS CHANGED TO A NEW |
| | OCCUPANCY CLASSIFICATION, SECTION 1012 SHALL APPLY. |
| | PLEASE UPDATE YOUR PLANS ACCORDINGLY. |
| | |
| | 1B) 2ND REVIEW COMMENT, NOT CHANGED. . SHEET S.2 |
| | INDICATES THE TENANT SPACE HAVING 1152 SQ. FT. THE |
| | INTERIOR TENANT SPACE WALLS SCALES 29.75 X 73= 973 |
| | GROSS SQ. FT. OF TENANT SPACE. FOR DAYCARE OCCUPANCY |
| | THE OCCUPANT LOAD IS SUPPOSED TO BE CALCULATED ON THE |
| | NET SQUARE FEET. FLOOR AREA, NET. THE AREAS USED FOR |
| | PERMANENT BUILDING COMPONENTS, SUCH AS SHAFTS, FIXED |
| | EQUIPMENT, THICKNESS OF WALLS, CORRIDORS STAIRWAYS, |
| | TOILET ROOMS, MECHANICAL ROOMS, AND CLOSETS ARE NOT |
| | INCLUDED IN NET FLOOR AREA. |
| | PLEASE PROVIDE AN ACCURATE NET OCCUPANT LOAD. WITH |
| | RESTROOMS AND WALL THICKNESS REMOVED TO A NET SQ. |
| | FOOTAGE OF APPROX. 807/35= 23 OCCUPANTS. |
| | |
| | 1C) COMPLIED. OCCUPANT LOAD FIGURED AT 35 SQ. FEET PER |
| | OCCUPANT. |
| | |
| | 1D) 2ND REVIEW COMMENT, NOT CHANGED. SHEET S.1 |
| | INDICATES THE TOTAL NET AREA FOR THE A/C LOADS TO BE |
| | 2,175 SQ. FT. WHEN THE TOTAL INTERIOR SQUARE FEET ARE |
| | 973 SQ, FT./ NET OF 807 SQ. FT. APPROX. WHY THE BIG |
| | DISCREPANCY??????? 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 1E)2ND REVIEW COMMENT, NOT CHANGED. PLEASE SPECIFY |
| | WHICH OF THE CHILDREN FACTORS BELOW THESE PLANS WERE |
| | DESIGNED TOO, PLANS INDICATE GROUP E NORMAL HAZARD |
| | PLEASE IDENTIFY AS TO SPECIFIC AGE GROUP. SHEET S.2 |
| | UNDER THE HEADING OF CODE ANALYSIS INDICATES THE |
| | OCCUPANCY AS AN (E) EDUCATIONAL OCCUPANCY. PLEASE |
| | INDICATE AS TO WHICH TYPE OF EDUCATIONAL FACILITY THIS |
| | USE WILL FALL INTO: |
| | |
| | 305.2 GROUP E, DAY CARE FACILITIES. THIS GROUP INCLUDES |
| | BUILDINGS AND STRUCTURES OR PORTIONS THEREOF OCCUPIED |
| | BY MORE THAN FIVE CHILDREN OLDER THAN 2 1/2 YEARS OF |
| | AGE WHO RECEIVE EDUCATIONAL, SUPERVISION OR PERSONAL |
| | CARE SERVICES FOR FEWER THAN 24 HOURS PER DAY. |
| | OR |
| | 308.6.1 CLASSIFICATION AS GROUP E. A CHILD DAY CARE |
| | FACILITY THAT PROVIDES CARE FOR MORE THAN FIVE BUT NO |
| | MORE THAN 100 CHILDREN 2 1/2 YEARS OR LESS OF AGE, |
| | WHERE THE ROOMS IN WHICH THE CHILDREN ARE CARED FOR ARE |
| | LOCATED ON A LEVEL OF EXIT DISCHARGE SERVING SUCH ROOMS |
| | AND EACH OF THESE CHILD CARE ROOMS HAS AN EXIT DOOR |
| | DIRECTLY TO THE EXTERIOR, SHALL BE CLASSIFIED AS GROUP |
| | E. |
| | OR |
| | CHILDREN 2 1/2 YEARS OF AGE OR LESS USUALLY ARE NOT |
| | ABLE TO RECOGNIZE AN EMERGENCY SITUATION, MAY NOT |
| | RESPOND APPROPRIATELY OR MAY NOT BE ABLE TO EGRESS |
| | WITHOUT ASSISTANCE; THUS FACILITIES THAT HAVE MORE THAN |
| | 5 CHILDREN 2 1/2 YEARS OF AGE OR LESS ARE CLASSIFIED AS |
| | CHILD CARE FACILITIES AND CONSIDERED TO BE |
| | GROUP I-4. |
| | |
| | 2ND REVIEW COMMENT, PLEASE DEFINE IF THIS FACILITY IS |
| | TO BE CONSIDERED A I-4 FACILITY OR WHAT TYPE OF GROUP E |
| | DAY CARE FACILITY? |
| | |
| | 1F) 2ND REVIEW COMMENT/ CHANGED SOMEWHAT. 2014 FBC-B |
| | 1015.6 DAY CARE MEANS OF EGRESS. DAY CARE FACILITIES, |
| | ROOMS OR SPACES WHERE CARE IS PROVIDED FOR MORE THAN 10 |
| | CHILDREN THAT ARE 2 1/2 YEARS OF AGE OR LESS, SHALL |
| | HAVE ACCESS TO NOT LESS THAN TWO EXITS OR EXIT ACCESS |
| | DOORWAYS. THIS SET OF PLANS IS DEFICIENT IN NOT SHOWING |
| | THE COMPLETE SITE PLAN, THE ORIGINAL DESIGNER SHOWED |
| | BEHIND THE TENANT SPACE A FENCED IN PLAY GROUND AND THE |
| | 2ND MEANS OF EGRESS TO THE PUBLIC WAY. THE CURRENT PLAN |
| | DOES NOT SHOW A 2ND MEANS OF EGRESS TO THE PUBLIC WAY. |
| | |
| | 1G) COMPLIED. FBC-B466.2 CLOSET DOORS. |
| | |
| | 1H) COMPLIED. FBC-B 466.3 BATHROOM DOORS. |
| | |
| | 2) 2ND REQUEST, NOT CHANGED. SHEET S.1 SHOWS THE FRONT |
| | ENTRY GOING INTO AN EXISTING HALLWAY, PLEASE BE AWARE |
| | THIS IS AN OPEN MALL BUILDING, SEE 2014 FBC-B 402.1. |
| | PLEASE REVISE PLANS. |
| | |
| | 3A) 2ND REQUEST. PLEASE SHOW CODE COMPLIANCE WITH 466.7 |
| | DETECTION AND ALARM SYSTEMS. DAY CARE OCCUPANCIES SHALL |
| | BE PROVIDED WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH |
| | SECTION 907 AND THIS SECTION, 466.7.1 & 466.7.1.1. FIRE |
| | ALARM LOW VOLTAGE BESIDES NEEDING TO BE ON THESE |
| | DOCUMENTS WILL ALSO REQUIRE A SEPARATE PERMIT. |
| | |
| | 3B) COMPLIED. 2014 FBC-B 466.7.2 DETECTION. |
| | |
| | 4) PLEASE NOTE THE FBC-B CHAPTER 468 SECTION OF THE |
| | CODE ALSO DEALS WITH SCHOOLS AND WOULD NEED TO BE |
| | REVIEWED FOR CODE COMPLIANCE. |
| | |
| | 4A) 2ND REQUEST. 468.2.2 PLAYGROUNDS AND EQUIPMENT. |
| | PLAYGROUNDS AND EQUIPMENT SHALL BE SAFE, STRUCTURALLY |
| | SOUND, VERMIN PROOF, AND SHALL NOT HAVE JAGGED OR SHARP |
| | PROJECTIONS. PLAYGROUND EQUIPMENT SHALL BE ANCHORED TO |
| | SUITABLE FOUNDATIONS TO PREVENT TOPPLING OR |
| | DISLODGEMENT. CUSHIONING MATERIALS SUCH AS MATS, WOOD |
| | CHIPS, OR SAND SHALL BE USED UNDER CLIMBING EQUIPMENT, |
| | SLIDES, AND SWINGS. |
| | |
| | 4B)2ND REQUEST. 468.2.3 OUTDOOR WASTE CONTAINERS. A |
| | SMOOTH NONABSORBENT SURFACE SHALL BE PROVIDED FOR |
| | OUTDOOR WASTE CONTAINERS. |
| | |
| | 4C) 2ND REQUEST. NOT SHOWN ON THE PLANS, THE CODE IS |
| | JUST REPEATED ON THE PLANS. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 468.3.4 DIAPER CHANGING STATIONS. A DIAPER CHANGING |
| | STATION SHALL BE LOCATED IN OR ADJACENT TO ANY |
| | CLASSROOM WHERE CHILDREN WEARING DIAPERS ARE IN |
| | ATTENDANCE. A HAND WASHING LAVATORY SHALL BE PROVIDED |
| | WITHIN THE CHANGING STATION AREA. ACCESS SHALL BE |
| | PROVIDED TO THE LAVATORY WITHOUT OPENING DOORS OR |
| | TOUCHING A HANDLE. |
| | |
| | 4D) 2ND REQUEST. 468.3.5.2 TEACHER TOILETS. FACULTY AND |
| | STAFF TOILETS SHALL BE SEPARATE FROM STUDENT TOILETS. |
| | |
| | 4E) 2ND REQUEST. 468.3.5.5 WALLS. WALLS IN TOILET ROOMS |
| | SHALL BE IMPERVIOUS TO A HEIGHT OF AT LEAST 4 FEET |
| | (1219 MM) ABOVE THE FLOOR. WALLS IN KITCHENS, |
| | SCULLERIES, CAN WASH AREAS, AND SHOWER ROOMS SHALL BE |
| | IMPERVIOUS TO A HEIGHT OF AT LEAST 6 FEET (1829 MM) |
| | ABOVE THE FLOOR. TOILET AND SHOWER PARTITIONS SHALL BE |
| | IMPERVIOUS. |
| | |
| | 4F) SEMI-COMPLIED, DOES NOT INDICATE THE AGE OF THE |
| | KIDS USING THESE FACILITIES. 2014 FBC-ACCESS. CODE |
| | 604.1 GENERAL. WATER CLOSETS AND TOILET COMPARTMENTS |
| | SHALL COMPLY WITH 604.2 THROUGH 604.8. EXCEPTION: WATER |
| | CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S USE |
| | SHALL BE PERMITTED TO COMPLY WITH 604.9. 604.9 WATER |
| | CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S USE. |
| | WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S |
| | USE SHALL COMPLY WITH 604.9. |
| | |
| | 4G-I) DELETED SHOWER. |
| | |
| | 5) COMPLIED. 2014FBC-B1008.1.10 PANIC AND FIRE EXIT |
| | HARDWARE |
| | |
| | 6) 2ND REQUEST. THERE ARE NEW WALLS WITHIN THE TENANT |
| | SPACE, FIRE SPRINKLERS MAY NEED TO BE MOVED TO ACHIEVE |
| | PROPER COVERAGE. PLEASE PROVIDE THE NEW FIRE SPRINKLER |
| | LAYOUT CEILING PLAN. 107.3.5 MINIMUM PLAN REVIEW |
| | CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | SCHEMATIC FIRE SPRINKLERS. |
| | |
| | 7) 2ND REQUEST. IMPACT FEES. BEFORE A PERMIT TO |
| | CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST |
| | BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| | (561)233-5025 FOR MORE INFORMATION. |
| | |
| | 8 ) 2ND REQUEST. WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS & |
| | REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |