Plan Review Notes
Plan Review Notes For Permit 16030552
Permit Number 16030552
Review Stop P
Sequence Number 2
Notes
Date Text
2016-06-30 15:29:431ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. THE 3 COMPARTMENT SINK SHALL CONNECT INDIRECTLY TO
 SANITARY. PER FBC PL SEC. 802.1.1 FOOD HANDLING.
 EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE,
 PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE
 THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP.
  
 2. THE 3 COMPARTMENT SINK IS REQUIRED TO DRAIN THROUGH
 A GREASE INTERCEPTOR. PER FBC PL SEC. 1003.3.1 GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES
 REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS.
  
 3. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1
  
 3. A DRINKING FOUNTAIN IS REQUIRED. PER FBC PL TABLE
 403.1
  
 4. ON SANITARY RISER DIAGRAM P3, FD-1 ARE NOT VENTED.
 PER FBC PL SEC.912.2.1
  
 5. ON WATER RISER DIAGRAM HOT OR TEMPERED-WATER IS
 REQUIRED FOR P-8,
  
 6. THE WATER HEATER DETAIL SHOWS RELIEF LINE WHERE WILL
 THIS DRAIN DISCHARGE. PER WPB AMEND TO FBC 107.2.1
  
 7. PLUMBING FIXTURE SCHEDULE SHOWS 1IN. CW FOR WATER
 CLOSETS THE WATER RISER DIAGRAM SHOWS 1/2IN. PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 8. SEPARATE FACILITY'S ARE REQUIRED FOR STAFF. PER FBC
 PL SEC. 403.2 SEPARATE FACILITIES.
 WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALL BE PROVIDED FOR EACH SEX.
  
 ACCESSIBILITY :
  
 1. ADULT TOILET AND BATHING ROOMS SHALL COMPLY WITH FBC
 ACC. SEC. 603-604
  
 603.2.1 TURNING SPACE.
 TURNING SPACE COMPLYING WITH 304 SHALL BE PROVIDED
 WITHIN THE ROOM.
  
 603.2.2 OVERLAP.
 REQUIRED CLEAR FLOOR SPACES, CLEARANCE AT FIXTURES, AND
 TURNING SPACE SHALL BE PERMITTED TO OVERLAP.
  
 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
  
 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH.
  
 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL
  
 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 604.5 GRAB BARS.
 GRAB BARS FOR WATER CLOSETS SHALL COMPLY WITH 609. GRAB
 BARS SHALL BE PROVIDED ON THE SIDE WALL CLOSEST TO THE
 WATER CLOSET AND ON THE REAR WALL.
  
 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE
 HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A
 BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1.
  
 2. CHILDREN'S TOILET ROOMS SHALL COMPLY WITH 604.9
 WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S
 USE.
 WATER CLOSETS AND TOILET COMPARTMENTS FOR CHILDREN?S
 USE SHALL COMPLY WITH 604.9.
  
 3. SHOWER COMPARTMENT SHALL COMPLY WITH 608
  
 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES
 (915 MM) BY 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS
 MEASURED AT THE CENTER POINTS OF OPPOSING SIDES AND
 SHALL HAVE A 36 INCH (915 MM) WIDE MINIMUM ENTRY ON THE
 FACE OF THE SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES
 (915 MM) WIDE MINIMUM BY 48 INCHES (1220 MM) LONG
 MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE
 PROVIDED.
  
 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE
 PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A
 POINT 18 INCHES (455 MM) FROM THE CONTROL WALL.
  
 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
  
 608.4 SEATS.
 A FOLDING OR NON-FOLDING SEAT SHALL BE PROVIDED IN
 TRANSFER TYPE SHOWER COMPARTMENTS. A FOLDING SEAT SHALL
 BE PROVIDED IN ROLL-IN TYPE SHOWERS REQUIRED IN
 TRANSIENT LODGING GUEST ROOMS WITH MOBILITY FEATURES
 COMPLYING WITH 806.2. SEATS SHALL COMPLY WITH 610.
  
  
 608.7 THRESHOLDS.
 THRESHOLDS IN ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE
 1/2 INCH (13 MM) HIGH MAXIMUM IN ACCORDANCE WITH 303.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THRESHOLDS 1/2
 INCH (13 MM) HIGH MAXIMUM SHALL BE BEVELED, ROUNDED, OR
 VERTICAL.
  
  
  