2016-08-11 17:02:50CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED.
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE (2) SETS OF MECHANICAL PLANS
 (2) PLANS MUST SHOW CONDITIONED AIR TO ALL AREAS. MANY
 SUPPLY DROPS ARE SHOWN IN WALLS. NEW OFFICE HAS NO
 SUPPLY DROP. RECEPTION AREA HAS NO SUPPLY DROP.
 (3) PROVIDE EXISTING DUCT SIZES AND GRILL SIZES.
 (4) SHOW EXHAUST SYSTEM FOR BATHROOMS.
 (5) PROVIDE EQUIPMENT SCHEDULE WITH EXISTING RTU.
 (6) PROVIDE PROPER AIR RETURN TO RTU.
  
 FLORIDA ENERGY CODE FBC 2014
  
 C101.4.4 CHANGE IN OCCUPANCY OR USE.
 SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD
 RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL
 OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE. WHERE
 THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE
 C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1)
 OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY
 WITH SECTION C405.5.
  
 (7) PROVIDE ENERGY CALCULATIONS
 (8) PROVIDE HEAT LOAD CALCULATIONS
  