2016-03-24 15:12:151) THE HEIGHT OF THE THREE COMPARTMENT SHALL BE A
 MAXIMUM OF 34 INCHES ABOVE THE FOOR. FAC SEC. 212.1.
 2) SHOW THE DRINKING FOUNTAINS ON THE SANITARY AND
 WATER RISER DIAGRAMS.FBC 107.3.5.1.3.
 3) THE DRINKING FOUNTAINS SHALL COMPLY WITH FAC SEC.
 307.2 FOR PROTRUDING OBJECTS. SUBMIT AN ELEVATION
 DETAIL SHOWING THE LEADING EDGE OF BOTH UNITS ABOVE THE
 FINISH FLOOR.
 4) INDICATE THE PREVIOUS OCCUPANCY OF THIS SPACE.FBC
 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  