| 2016-03-30 11:24:03 | PERMIT # 16030552 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION |
| | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND |
| | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION |
| | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A |
| | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A |
| | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED |
| | BY EMAIL ([email protected]) OR IN WRITING (FAX: |
| | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? |
| | |
| | 3) DRAWING NOTE ON SHEET A1.01 INDICATES THAT ALL FIRE |
| | SPRINKLER AND FIRE ALARM SYSTEMS TO REMAIN. A LIFE |
| | SAFETY ENGINEER SHOULD COMPLETE A FORMAL EVALUATION TO |
| | VERIFY THAT NO MODIFICATIONS ARE NEEDED TO THE EXISTING |
| | FIRE AND LIFE SAFETY SYSTEMS. SHOULD MODIFICATIONS BE |
| | REQUIRED, SEPARATE PLANS AND PERMITS ARE REQUIRED FOR |
| | THE INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | |
| | 4) ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS |
| | SHALL NOT EXCEED 50 PERCENT OF THE INDIVIDUAL WALL |
| | AREA. |
| | |
| | 5) SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL |
| | RECEPTACLES SHALL BE INSTALLED IN ALL AREAS OCCUPIED BY |
| | CLIENTS. |
| | |
| | 6) AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN |
| | BUILDING PRIOR TO OCCUPANCY. |
| | EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL |
| | DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM. |
| | |
| | 7) FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED |
| | MONTHLY BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER |
| | WHICH A COPY OF THE LATEST INSPECTION REPORT SHALL BE |
| | POSTED IN A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. |
| | IT SHALL BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS |
| | DAILY TO ENSURE THAT ALL DOORS AND EXIT PATHS ARE |
| | MAINTAINED CLEAR OF OBSTRUCTIONS. |
| | |
| | 8) REVIEW AND ADDRESS COMMENTS LISTED UNDER BUILDING |
| | PLAN REVIEW. |
| | |
| | |
| | SUE ELLEN CALDERON |
| | ASSISTANT FIRE MARSHAL |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 644-7326 |
| | |