| 2016-03-17 12:54:44 | |
| | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030552 |
| | ADD: 6901 OKEECHOBEE BLVD. |
| | CONT: RANDOLPH & DEWDNEY CONSTRUCTION |
| | TEL: 561-276-2889 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. MAR. 17/2016 |
| | ACTION: DENIED |
| | |
| | 1A) SHEET A-0.00 UNDER THE HEADING OF CODE ANALYSIS |
| | INDICATES THE OCCUPANCY AS AN (E) EDUCATIONAL |
| | OCCUPANCY. PLEASE INDICATE AS TO WHICH TYPE OF |
| | EDUCATIONAL FACILITY THIS USE WILL FALL INTO: |
| | |
| | 305.2 GROUP E, DAY CARE FACILITIES. THIS GROUP INCLUDES |
| | BUILDINGS AND STRUCTURES OR PORTIONS THEREOF OCCUPIED |
| | BY MORE THAN FIVE CHILDREN OLDER THAN 21/2 YEARS OF AGE |
| | WHO RECEIVE EDUCATIONAL, SUPERVISION OR PERSONAL CARE |
| | SERVICES FOR FEWER THAN 24 HOURS PER DAY. |
| | |
| | |
| | 308.6.1 CLASSIFICATION AS GROUP E. |
| | A CHILD DAY CARE FACILITY THAT PROVIDES CARE FOR MORE |
| | THAN FIVE BUT NO MORE THAN 100 CHILDREN 21/2 YEARS OR |
| | LESS OF AGE, WHERE THE ROOMS IN WHICH THE CHILDREN ARE |
| | CARED FOR ARE LOCATED ON A LEVEL OF EXIT DISCHARGE |
| | SERVING SUCH ROOMS AND EACH OF THESE CHILD CARE ROOMS |
| | HAS AN EXIT DOOR DIRECTLY TO THE EXTERIOR, SHALL BE |
| | CLASSIFIED AS GROUP E. |
| | |
| | CHILDREN 2 1/2 YEARS OF AGE OR LESS USUALLY ARE NOT |
| | ABLE TO RECONIZE AN EMERGENCY SITUATION, MAY NOTRESPOND |
| | APPROPRIATELY OR MAY NOT BE ABLE TO EGRESS WITHOUT |
| | ASSISTANCE; THUS FACILITIES THAT HAVE MORE THAN 5 |
| | CHILDREN 2 1/2 YEARS OF AGE OR LESS ARE CLASSIFIED AS |
| | CHILD CARE FACILITES AND CONSIDERED TO BE GROUP I-4. |
| | |
| | THE COVERSHEET INDICATES THIS TO BE A EARLY CHILDHOOD |
| | LEARNING CENTER. PLEASE DEFINE IF THIS FACILITY IS TO |
| | BE CONSIDERED A I-4 FACILITY OR GROUP E DAY CARE |
| | FACILITY? |
| | |
| | 1B) 2014 FBC-B 1015.6 DAY CARE MEANS OF EGRESS. DAY |
| | CARE FACILITIES, ROOMS OR SPACES WHERE CARE IS PROVIDED |
| | FOR MORE THAN 10 CHILDREN THAT ARE 21/2 YEARS OF AGE OR |
| | LESS, SHALL HAVE ACCESS TO NOT LESS THAN TWO EXITS OR |
| | EXIT ACCESS DOORWAYS. |
| | |
| | 1C) FBC-B466.2 CLOSET DOORS. EVERY CLOSET DOOR LATCH |
| | SHALL BE SUCH THAT CLIENTS CAN OPEN THE DOOR FROM |
| | INSIDE THE CLOSET. |
| | |
| | 1D) FBC-B 466.3 BATHROOM DOORS. EVERY BATHROOM DOOR |
| | LOCK SHALL BE DESIGNED TO PERMIT OPENING OF THE LOCKED |
| | DOOR FROM THE OUTSIDE IN AN EMERGENCY. THE OPENING |
| | DEVICE SHALL BE READILY ACCESSIBLE TO THE STAFF. |
| | |
| | |
| | 2) PLEASE SHOE CODE COMPLIANCE WITH 466.7 DETECTION AND |
| | ALARM SYSTEMS. DAY CARE OCCUPANCIES SHALL BE PROVIDED |
| | WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION 907 |
| | AND THIS SECTION, 466.7.1 & 466.7.1.1. |
| | |
| | 3) 2014 FBC-B 466.7.2 DETECTION. A SMOKE DETECTION |
| | SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72, |
| | WITH PLACEMENT OF DETECTORS IN EACH STORY IN FRONT OF |
| | DOORS TO THE STAIRWAYS AND IN THE CORRIDORS OF ALL |
| | FLOORS OCCUPIED BY THE DAY CARE OCCUPANCY. DETECTORS |
| | ALSO SHALL BE INSTALLED IN LOUNGES, RECREATION AREAS |
| | AND SLEEPING ROOMS IN THE DAY CARE OCCUPANCY. |
| | |
| | 4) 2014 FBC-B 466.8 CORRIDORS. EVERY INTERIOR CORRIDOR |
| | SHALL BE CONSTRUCTED OF WALLS HAVING NOT LESS THAN A |
| | 1-HOUR FIRE-RESISTANCE RATING. |
| | EXCEPTION: |
| | 1. IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH SECTIONS 901.6 AND 903.3.1.1, CORRIDOR WALLS SHALL |
| | NOT BE REQUIRED TO BE RATED, PROVIDED THAT SUCH WALLS |
| | FORM SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 710. |
| | |
| | 2. WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING |
| | 1-HOUR FIRE-RESISTANCE RATING WHERE TESTED AS A WALL, |
| | THE CORRIDOR WALLS SHALL BE PERMITTED TO TERMINATE AT |
| | THE CORRIDOR CEILING. |
| | |
| | 5) PLEASE NOTE THE FBC-B CHAPTER 468 SECTION OF THE |
| | CODE ALSO DEALS WITH SCHOOLS AND WOULD NEED TO BE |
| | REVIEWED FOR CODE COMPLIANCE. |
| | |
| | 6) SHEET A-1.01 THE FRONT DOOR EXISTING (000) AND REAR |
| | EXTERIOR DOOR (011) ALSO EXISTING ARE SHOWN ON THIS |
| | PLAN. SHEET A-1.02 THE DOOR SCHEDULE INDICATES THESE |
| | DOORS WITH DOOR HARDWARE TYPE 5 EXISITNG DOOR, FRAME |
| | AND HARDWARE. |
| | |
| | PLEASE NOTE THIS IS A CHANGE IN OCCUPANCY FROM |
| | MERCANTILE TO EDUCATIONAL. UNDER THE 2014 EXISTING |
| | BUILDING CODE 1012.4 MEANS OF EGRESS. |
| | EXST. BLDG CODE 1012.4.2 MEANS OF EGRESS FOR CHANGE OF |
| | USE TO EQUAL OR LOWER HAZARD CATEGORY. WHEN A CHANGE OF |
| | OCCUPANCY CLASSIFICATION IS MADE TO AN EQUAL OR LESSER |
| | HAZARD CATEGORY (HIGHER NUMBER) AS SHOWN IN TABLE |
| | 1012.4, EXISTING ELEMENTS OF THE MEANS OF EGRESS SHALL |
| | COMPLY WITH THE REQUIREMENTS OF SECTION 905 FOR THE NEW |
| | OCCUPANCY CLASSIFICATION. NEWLY CONSTRUCTED OR |
| | CONFIGURED MEANS OF EGRESS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 2014FBC-B1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS |
| | SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR |
| | MORE IN A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED |
| | WITH A LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR |
| | FIRE EXIT HARDWARE. |
| | |
| | 2014 EXST. BLDG. CODE. 805.4.4.1 SUPPLEMENTAL |
| | REQUIREMENTS FOR PANIC HARDWARE. WHERE THE WORK AREA |
| | EXCEEDS 50 PERCENT OF THE FLOOR AREA, PANIC HARDWARE |
| | SHALL COMPLY WITH SECTION 805.4.4 THROUGHOUT THE FLOOR. |
| | |
| | 7) SHEET A-1.01 THE REAR EXIT LEADS INTO A FENCED |
| | EXTERIOR PLAYGROUND WITH A GATE. THERE IS A NOTE THAT |
| | THE GATE WILL HAVE A VERTICAL PULL GATE LATCH. |
| | |
| | 2014 FBC-B 1008.2 GATES. GATES SERVING THE MEANS OF |
| | EGRESS SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF |
| | THIS SECTION. GATES USED AS A COMPONENT IN A MEANS OF |
| | EGRESS SHALL CONFORM TO THE APPLICABLE REQUIREMENTS FOR |
| | DOORS. |
| | |
| | 2014FBC-B1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS |
| | SERVING ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR |
| | MORE IN A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED |
| | WITH A LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR |
| | FIRE EXIT HARDWARE. |
| | |
| | 8) SHEET A-0.00 THE CODE ANALYSIS INDICATES AN OCCUPANT |
| | LOAD OF 59 OCCUPANTS. SECTION 1015.1(1) OF THE |
| | FBC-BUILDING CODE REQUIRES 2 MEANS OF EGRESS WHEN A |
| | OCCUPANT LOAD IS GREATER THAN 49. PLEASE REVIEW THE |
| | 2014 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| | EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | |
| | PLEASE PROVIDE HOW CODE COMPLIANCE WILL BE MET FROM THE |
| | REAR EXIT DOOR (EXIT DISCHARGE) TO THE PUBLIC WAY. |
| | |
| | 9) SHEET A-1.02 DETAIL #5 SHOWS THE 3 COMPARTMENT SINK |
| | AT A HEIGHT OF 36 INCHES PLEASE PROVIDE COMPLIANCE WITH |
| | 2014 FBC-ACCESS. CODE 606.3 HEIGHT OF 34 INCHES TO THE |
| | RIM OR COUNTER SURFACE. |
| | |
| | 10) SHEET A-1.01 THE RESTROOMS IF THIS IS A FACILITY |
| | FOR YOUNG CHILDREN ARE GOING TO BE FACILITIES AGE |
| | APPROPRIATE FACILIIES THAT WILL SHOW COMPLIANCE WITH |
| | THE 2014 FBC-ACCESSIBLITY CODE 604.9. |
| | |
| | 11) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |