| Plan Review Notes For Permit 16030508 |
| Permit Number |
16030508 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-21 15:28:53 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16030508 | | | 3/21/16 | | | | | | 1) THE SUMMARY AC CALCULATIONS REQUIRE AN ENGINEERS | | | SIGNATURE AND SEAL PER SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION. PLEASE CLARIFY WHY THERE IS NO | | | VENTILATION AIR FOR OCCUPANTS SHOWN ON THE CALCS. | | | 2) PROVIDE A DOOR SCHEDULE THAT INDICATES THE TYPE OF | | | AND SIZE OF LOUVERED DOORS AT THE AC CLOSETS- REFER TO | | | SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION. | | | 3) THE CORRIDOR (HALLWAY 206) CANNOT SERVE AS A RETURN | | | AIR DUCT FOR AHU-2- SEE SECTION 601.2 FBC-14 | | | MECHANICAL. | | | 4) THE AC SCHEDULE INDICATES A TOTAL OF 1600 CFM'S OF | | | SUPPLY AIR FOR AHU-2, HOWEVER THE PLAN SHOWS A TOTAL OF | | | 1795 CFM'S BEING DISTRIBUTED IN THE ZONE. | | | 5) ALL NEW DUCT SMOKE DETECTORS SHALL BE INSTALLED IN | | | THE RETURN AIR SYSTEMS OF THE AIR HANDLERS PER SECTION | | | 606.2.1 FBC-14 MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|