| 2016-03-22 12:56:20 | 1ST ELECTRICAL REVIEW NOTES FOR REVISION #:16030508 |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 |
| | NFPA 70 2011 (NEC) |
| | |
| | CORRECTIONS REQUIRED: |
| | SHEET E0.1 |
| | 1. DEMOLITION NOTES 10 HAVE UNDEFINED CODE QUOTED. SEE |
| | CURRENT ADOPTED APPLICABLE CODE WHICH MAY NOT |
| | NECESSARILY BE THE LATEST EDITIONS. |
| | 2. SHEET E1.1 ELECTRICAL POWER PLAN IS MISSING. PLEASE |
| | PROVIDE THIS SHEET FOR REVIEW. PLEASE NOTE THAT THE |
| | FAILURE TO INCLUDE THIS SHEET IN THE INITIAL SUBMITTAL |
| | MAY CREATE THE NEED FOR A SECOND RESUBMITTAL AS THIS |
| | PAGE IS REVIEWED. |
| | SHEET E2.1 |
| | 1. IN ADDITION TO THE LIGHTING CONTROLLED MENTIONED. |
| | COMPLIANCE W/FBC-EC405.2.2.3 DAYLIGHT ZONES SHALL BE |
| | CONTROLLED SEPARATELY. |
| | 2. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. |
| | SHEET E3.1 |
| | 1. NEC 110.16 ARC-FLASH HAZARD WARNING LABELS REQUIRED |
| | ON ALL ELECTRICAL APPARATUS. |
| | 2. NEC 110.24 MAXIMUM AVAILABLE FAULT CURRENT SHALL BE |
| | DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS. |
| | 3. NEC 408.4(B) ALL SWITCHBOARDS AND PANELBOARDS |
| | SUPPLIED BY A FEEDER IN OTHER THAN A ONE OR TWO FAMILY |
| | DWELLING SHALL BE MARKED TO INDICATE THE LOCATION AND |
| | TYPE OF THE SOURCE OF POWER. |
| | SHEET E5.1 |
| | 1. INCLUDE THE PROPOSED FIRE STOPPING DETAIL FOR |
| | ELECTRICAL OUTLET BOX IN A RATED WALL. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |