| 2016-03-21 10:45:23 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030508 |
| | ADD: 477 S. ROSEMARY SUITE # 230 |
| | CONT: TBD |
| | TEL: 684-6844/ NIKI BENNETT |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. MARCH 21/2016 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE REVIEW SHEET 004_A1.0 CORRIDOR 206 AND SHEET |
| | 16044_M1_1. PLEASE REVIEW 2014 FBC-B 1018.5 AIR |
| | MOVEMENT IN CORRIDORS. CORRIDORS SHALL NOT SERVE AS |
| | SUPPLY, RETURN, EXHAUST, RELIEF OR VENTILATION AIR |
| | DUCTS. THE MECHANICAL PLANS SHOW THE RETURN AIR IS |
| | BEING PULLED DOWN THRU THE CEILING ABOVE INTO THE |
| | CORRIDOR AND INTO THE AIR HANDLER CLOSET 209. THE DOOR |
| | SCHEDULE INDICATES THIS DOOR IS A WOOD LOUVERED DOOR. |
| | THE 2014 FBC-M DOES NOT ALLOW COMBUSTIBLE MATERIALS |
| | WITHIN PLENUMS. THE SAME ISSUE WITH DOOR 224B, NO |
| | COMBUSTIBLES ALLOWED WITHIN PLENUMS. |
| | |
| | NOTE FBC-B 1018.5 EXC. # 3 IS FOR OFFICES LESS THAN |
| | 1,000 SQ. FT. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |