| 2016-04-15 16:31:57 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET LSD 101 - A DOOR IS INDICATED IN A CORRIDOR TO |
| | REDUCE A DEADEND. ADDING A DOOR DOES NOT ALWAYS RELIEVE |
| | THE REQUIREMNT. PLEASE PROVIDE THE LIFE SAFETY CODE |
| | REFERENCE AND THE DIMENSIONS OF THE ENTIRE CORRIDOR. IT |
| | IS NOT ALWAYS APPROPRAITE TO JUST ADD A DOOR. THE DOOR |
| | MAY BE ABLE TO BE REMOVED BY PROVIDING A TEMPOARAY WALL |
| | AT THE RESTROOM C171 DOOR. |
| | |
| | 2) SHEET LSD 101 - REVERSE SWING DOOR OR REMOVE IS |
| | INDICATED AT THE DOUBLE DOORS AT ROOM C105. REMOVING |
| | THOSE DOOR MAY NOT BE AN OPTION AS IT MAY BE A REQUIRED |
| | RATED SEPARATION. PLEASE REVIEW AND ADDRESS. |
| | |
| | 3) SHEET LSD 101 - PROVIDE FOR AN EXIT SIGN AT THE |
| | DOUBLE DOORS AT ROOM C105 AND ALL OTHER REVERSED SWING |
| | DOORS APPROPRIATE IN THE CORRECT DIRECTION. |
| | |
| | 4) SHEET LSD 101 - ENSURE THAT ALL REVERSED SWING DOOR |
| | AR INSTALLED WITH THE PROPER AND APPROPRAITE EXIT |
| | HARDWARE DEVICES AS REQUIRED BY NFPA 101, CHAPTER 7, |
| | MEANS OF EGRESS. I.E PANIC HARDWARE, DOOR CLOSERS. |
| | |
| | 5) SHEET LSD 101 - AT EXIT E IT IS INDICATED EXIT |
| | DISCHARGE PROVIDED DURING CONSTRUCTION. PLEASE PROVIDE |
| | DETAIL OR AN EXPLANATION NOTE AS TO HOW IT IT WILL BE |
| | PROVIDED. |
| | |
| | 6) SHEET D 0001 - ADD A NOTE FOR FIRE ALARM AND FIRE |
| | SPRINKLER REMAINING ACTIVE THAT INDICATES "ANY TIME |
| | THAT WORK ON THE LIFE SAFETY SYSTEM, EXCEEDS 4 HOURS, A |
| | FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL |
| | FULL AND COMPLETE PROTECTION IS RETURNED". |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |