Plan Review Notes
Plan Review Notes For Permit 16030500
Permit Number 16030500
Review Stop E
Sequence Number 2
Notes
Date Text
2016-03-23 11:13:47PROVISO
  
 - SPOKE TO PROJECT MANAGER AND HE STATED HE WILL
 INSTALL A DISCONNECT AHEAD OF THE MLO PANELBOARD TO
 PROTECT SECONDARY CONDUCTORS FOR 150 KVA STEP DOWN
 TRANSFORMER FOR THE TEMPORARY OF THE BRISTOL. NEC
 450.3B , NEC 240.21C, NEC 408.36