| Notes |
| Date |
Text |
| 2016-03-23 11:13:47 | PROVISO | | | | | | - SPOKE TO PROJECT MANAGER AND HE STATED HE WILL | | | INSTALL A DISCONNECT AHEAD OF THE MLO PANELBOARD TO | | | PROTECT SECONDARY CONDUCTORS FOR 150 KVA STEP DOWN | | | TRANSFORMER FOR THE TEMPORARY OF THE BRISTOL. NEC | | | 450.3B , NEC 240.21C, NEC 408.36 |
|