Plan Review Notes
Plan Review Notes For Permit 16030500
Permit Number 16030500
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-14 10:40:32REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, FEEDER SCHEDULES AND EQUIPMENT SPEC.
  
 - SINCE DIRECTIONAL BOARING WILL BE TAKING PLACE IN THE
 RIGHT A WAY AN ENGINNERING PERMIT IS REQUIRED
  
 - PROVIDE A SITE PLAN TO INCLUDE ROUTING OF SERVICE
 CONDUCTORS , TRANSFORMER LOCATIONS , AND ELECTRICAL
 APPARATUS LOCATIONS IN RELATION TO EACH OTHER.
  
 - PROVIDE ADEQUATE PROTECTION TO ALL ELECTRICAL
 EQUIPMENT MOUNTED ON RACKS WITH POINTY SHARP EDGEES
 EXTENDING OUT WERE SUBJECT TO ACCIDENTAL CONTACT.
  
 - PLEASE COMPLY WITH THE FOLLOWING CODE SECTIONS NEC
 110.9 & 110.10 AIC RATING OF EQUIPMENT & PROTECTIVE
 DEVICES, NEC 110.15 HIGH LEG MARKING, NEC 110.16
 ARC-FLASH HAZARD WARNING, NEC 110.24
 AVAILABLE FAULT CURRENT FIELD MARKINGS, NEC 110.27
 GUARDING OF LIVE PARTS, NEC 300.6 PROTECTION AGAINST
 CORROSION , AND PROPERLY LABEL ALL DISCCONECTS.