| Plan Review Notes For Permit 16030500 |
| Permit Number |
16030500 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-14 10:40:32 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, FEEDER SCHEDULES AND EQUIPMENT SPEC. | | | | | | - SINCE DIRECTIONAL BOARING WILL BE TAKING PLACE IN THE | | | RIGHT A WAY AN ENGINNERING PERMIT IS REQUIRED | | | | | | - PROVIDE A SITE PLAN TO INCLUDE ROUTING OF SERVICE | | | CONDUCTORS , TRANSFORMER LOCATIONS , AND ELECTRICAL | | | APPARATUS LOCATIONS IN RELATION TO EACH OTHER. | | | | | | - PROVIDE ADEQUATE PROTECTION TO ALL ELECTRICAL | | | EQUIPMENT MOUNTED ON RACKS WITH POINTY SHARP EDGEES | | | EXTENDING OUT WERE SUBJECT TO ACCIDENTAL CONTACT. | | | | | | - PLEASE COMPLY WITH THE FOLLOWING CODE SECTIONS NEC | | | 110.9 & 110.10 AIC RATING OF EQUIPMENT & PROTECTIVE | | | DEVICES, NEC 110.15 HIGH LEG MARKING, NEC 110.16 | | | ARC-FLASH HAZARD WARNING, NEC 110.24 | | | AVAILABLE FAULT CURRENT FIELD MARKINGS, NEC 110.27 | | | GUARDING OF LIVE PARTS, NEC 300.6 PROTECTION AGAINST | | | CORROSION , AND PROPERLY LABEL ALL DISCCONECTS. |
|