| 2016-04-11 12:46:02 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16030488 |
| | ADD: 900 S. OLIVE AVE./ 10 DORMS 201,202,307, 308, 309, |
| | 407, 408, 409, 505 & 506. |
| | CONT: ROBLING ARCHITECTURE CONSTRUCTION, INC. |
| | TEL: 561-649-6705 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. APRIL 11/ 2016 |
| | ACTION: DENIED |
| | |
| | 1A) 2ND REQUEST. SHEET A-2 SHOWS A NEW EXTERIOR INSWING |
| | DOOR. THERE WERE NO PRODUCT APPROVALS IN THIS SUBMITTAL |
| | PACKAGE FOR A INSWING DOOR. . FLORIDA DEPARTMENT OF |
| | COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. INSWING. |
| | NOTE: SHEET A-4 DOES HAVE A OUTSWING DOOR. CHEM-PRUF |
| | DOOR ?OUTSWING DOOR TECHNICAL SHEETS WAS SUBMITTED BUT |
| | THERE IS NO COVERSHEET SHOWING IT TO BE A MIAMI-DADE |
| | NOA OR FLORIDA APPROVAL AND UNDER WHICH CODE THE |
| | APPROVAL WAS GIVEN. |
| | |
| | 1B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 1C) COMPLIED / WIND DESIGN CRITERIA. |
| | |
| | 1D) COMPLIED FLOOR SOUND INSULATION FOR TILE. ASTM E |
| | 492/ ASTM E 90 & ASTM 84 OR UL 723 |
| | |
| | 2) COMPLIED FLOOR SOUND INSULATION FOR TILE. ASTM E |
| | 492/ ASTM E 90 & ASTM 84 OR UL 723 |
| | |
| | 3A-B) COMPLIED. SHEET A-4 A NEW OUTSWING EXTERIOR DOOR. |
| | |
| | 3C) COMPLIED. |
| | |
| | |
| | 4-5) COMPLIED |
| | |
| | 6A) 2ND REQUEST. THE RESPONSE INDICATES COMPLIANCE WITH |
| | THE ADA OF 1990 SECTION 202.3: EXCEPTION3. |
| | PLEASE SEE THE SECTIONS LISTED BELOW ARE UNDER THE |
| | FLORIDA ACCESSIBILITY CODE ENACTED BECAUSE OF |
| | REMODELING, ALTERATIONS TO THE BUILDING. THE ONLY |
| | RELIEF TO THIS PORTION OF THE CODE LISTED BELOW AND ALL |
| | SECTIONS IS THE 20% DISPROPORTIONATE COST. THE ACCESS. |
| | CODE REQUIRES 20% OF THE CONTRACT VALUE OR AN |
| | ADDITIONAL $40,000.00 DOLLARS BE SPENT IN ACCESSIBLE |
| | UPGRADES AS LISTED BELOW. IF FULL COMPLIANCE CANNOT BE |
| | ACCOMPLISHED WITH THE $40,000.00 DOLLARS THEN AN |
| | ITEMIZED LIST OF HOW THE FUNDS ARE TO BE SPENT IN THE |
| | FOLLOWING ORDER, PLEASE HAVE THE ITEMIZED LIST ON |
| | EITHER THE ARCHITECTS OR CONTRACTORS LETTERHEAD. |
| | |
| | 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF |
| | DISPROPORTIONALITY. |
| | WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| | OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| | DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| | ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| | ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| | FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| | ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| | ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| | DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| | ALARMS. |
| | |
| | |
| | COMMENTS FROM THE 1ST REVIEW. |
| | PLEASE NOTE THE PLANS AND PERMIT APPLICATION INDICATE |
| | THE RENOVATION OF 10 DORMITORY ROOMS. PLEASE REVIEW |
| | SECTION 224.7 OF THE 2014 FBC-ACCESSIBILITY CODE. 224.7 |
| | HOUSING AT A PLACE OF EDUCATION. HOUSING AT A PLACE OF |
| | EDUCATION SHALL COMPLY WITH THE REQUIREMENTS FOR |
| | TRANSIENT LODGING GUEST ROOMS IN SECTIONS 224 AND 806, |
| | SUBJECT TO THE FOLLOWING EXCEPTIONS. THE TERM SLEEPING |
| | ROOM IS INTENDED TO BE USED INTERCHANGEABLY WITH THE |
| | TERM GUEST ROOM AS IT IS USED IN THE TRANSIENT LODGING |
| | STANDARDS. |
| | |
| | FBC - ACCESS. CODE 224.1.1 ALTERATIONS. |
| | WHERE GUEST ROOMS ARE ALTERED OR ADDED, THE |
| | REQUIREMENTS OF 224 SHALL APPLY ONLY TO THE GUEST ROOMS |
| | BEING ALTERED OR ADDED UNTIL THE NUMBER OF GUEST ROOMS |
| | COMPLIES WITH THE MINIMUM NUMBER REQUIRED FOR NEW |
| | CONSTRUCTION. |
| | ADVISORY 224.1.1 ALTERATIONS. |
| | IN ALTERATIONS AND ADDITIONS, THE MINIMUM REQUIRED |
| | NUMBER OF ACCESSIBLE GUEST ROOMS IS BASED ON THE TOTAL |
| | NUMBER OF GUEST ROOMS ALTERED OR ADDED INSTEAD OF THE |
| | TOTAL NUMBER OF GUEST ROOMS PROVIDED IN A FACILITY. |
| | TYPICALLY, EACH ALTERATION OF A FACILITY IS LIMITED TO |
| | A PARTICULAR PORTION OF THE FACILITY. WHEN ACCESSIBLE |
| | GUEST ROOMS ARE ADDED AS A RESULT OF SUBSEQUENT |
| | ALTERATIONS, COMPLIANCE WITH 224.5 (DISPERSION) IS MORE |
| | LIKELY TO BE ACHIEVED IF ALL OF THE ACCESSIBLE GUEST |
| | ROOMS ARE NOT PROVIDED IN THE SAME AREA OF THE |
| | FACILITY. |
| | |
| | 6B) FBC-ACCESS. CODE 224.4 GUEST ROOMS WITH |
| | COMMUNICATION FEATURES. |
| | IN TRANSIENT LODGING FACILITIES, GUEST ROOMS WITH |
| | COMMUNICATION FEATURES COMPLYING WITH 806.3 SHALL BE |
| | PROVIDED IN ACCORDANCE WITH TABLE 224.4. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | |