| 2016-03-15 16:46:34 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16030488 | | | 3/15/16 | | | | | | 1) PROVIDE AC CHANGE OUT FORMS FOR ALL THE PROPOSED AHU | | | AND FAN COIL REPLACEMENTS. | | | 2) PROVIDE AN INSTALLATION DETAIL FOR AHU-201 SHOWING | | | HOW THE UNIT WILL BE ATTACHED AND SUPPORTED FROM THE | | | STRUCTURE. PLEASE INCLUDE THE DETAILS FOR THE PRIMARY | | | AND AUXILIARY CONDENSATE DISPOSAL SYSTEMS. | | | 3) SHEET MVP-1: PROVIDE A VENTILATION AIR CALCULATION. | | | 4) CLARIFY IF THE EXISTING CHILLER/CONDENSER SYSTEM IIS | | | BEING REPLACED AND PROVIDE DETAILS IF APPLICABLE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|