2016-03-15 16:46:341ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030488
 3/15/16
  
 1) PROVIDE AC CHANGE OUT FORMS FOR ALL THE PROPOSED AHU
 AND FAN COIL REPLACEMENTS.
 2) PROVIDE AN INSTALLATION DETAIL FOR AHU-201 SHOWING
 HOW THE UNIT WILL BE ATTACHED AND SUPPORTED FROM THE
 STRUCTURE. PLEASE INCLUDE THE DETAILS FOR THE PRIMARY
 AND AUXILIARY CONDENSATE DISPOSAL SYSTEMS.
 3) SHEET MVP-1: PROVIDE A VENTILATION AIR CALCULATION.
 4) CLARIFY IF THE EXISTING CHILLER/CONDENSER SYSTEM IIS
 BEING REPLACED AND PROVIDE DETAILS IF APPLICABLE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER