Plan Review Notes
Plan Review Notes For Permit 16030488
Permit Number 16030488
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-15 10:58:52INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE A GENERAL NOTE TO INDICATE REQUIRED
 SEPARATE PERMITS FOR ALL LOW VOLTAGE SYSTEMS SHOWN ON
 SCOPE. FBC 107.3.5
 2. PLEASE PROVIDE A PANEL SCHEDULE FOR REFERENCE AS TO
 WHAT CIRCUIT DESIGNATION WILL POWER OR ENERGIZE THE NEW
 LIGHTING AND RECEPTACLES OUTLETS AND LABEL THE FLOOR
 PLAN WITH THE CIRCUIT DESIGNATION. FBC 107.3.5
 3. PROVIDE GENERAL NOTES TO REFLECT REQUIRED AFCI
 PROTECTED CIRCUITS AND TAMPER RESISTANT RECEPTACLES PER
 NEC 210.12A AND 406.12. A NOTE WILL SUFFICE
 4. ADDRESS WALL SPACE REQUIREMENTS FOR RECEPTACLE
 OUTLET THROUGHOUT UNITS SHOWN. NEC 210.52A2
 5. ADDRESS COUNTER WALL SPACE REQUIREMENTS FOR
 RECEPTACLE OUTLET THROUGHOUT KITCHEN UNITS SHOWN. NEC
 210.52C1
 6. SHOW THE REQUIRED OUTDOOR BALCONY RECEPTACLE OUTLETS
 PER NEC 210.52E3
 7. SHOW THE SMOKE DETECTOR PLACEMENT PER FBC RES 314
 REQUIREMENTS.
 8. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL
 FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE
 ANY QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  