| 2016-03-15 10:58:52 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE PROVIDE A GENERAL NOTE TO INDICATE REQUIRED | | | SEPARATE PERMITS FOR ALL LOW VOLTAGE SYSTEMS SHOWN ON | | | SCOPE. FBC 107.3.5 | | | 2. PLEASE PROVIDE A PANEL SCHEDULE FOR REFERENCE AS TO | | | WHAT CIRCUIT DESIGNATION WILL POWER OR ENERGIZE THE NEW | | | LIGHTING AND RECEPTACLES OUTLETS AND LABEL THE FLOOR | | | PLAN WITH THE CIRCUIT DESIGNATION. FBC 107.3.5 | | | 3. PROVIDE GENERAL NOTES TO REFLECT REQUIRED AFCI | | | PROTECTED CIRCUITS AND TAMPER RESISTANT RECEPTACLES PER | | | NEC 210.12A AND 406.12. A NOTE WILL SUFFICE | | | 4. ADDRESS WALL SPACE REQUIREMENTS FOR RECEPTACLE | | | OUTLET THROUGHOUT UNITS SHOWN. NEC 210.52A2 | | | 5. ADDRESS COUNTER WALL SPACE REQUIREMENTS FOR | | | RECEPTACLE OUTLET THROUGHOUT KITCHEN UNITS SHOWN. NEC | | | 210.52C1 | | | 6. SHOW THE REQUIRED OUTDOOR BALCONY RECEPTACLE OUTLETS | | | PER NEC 210.52E3 | | | 7. SHOW THE SMOKE DETECTOR PLACEMENT PER FBC RES 314 | | | REQUIREMENTS. | | | 8. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL | | | FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE | | | ANY QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|