| Plan Review Notes For Permit 16030480 |
| Permit Number |
16030480 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-14 10:34:25 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE PROVIDE A PANEL SCHEDULE FOR REFERENCE AS TO | | | WHAT CIRCUIT DESIGNATION WILL POWER OR ENERGIZE THE NEW | | | LIGHTING AND RECEPTACLES OUTLETS AND LABEL THE FLOOR | | | PLAN WITH THE CIRCUIT DESIGNATION. FBC 107.3.5 | | | 2. PROVIDE A NOTE TO COMPLY WITH NEC 410.130G- | | | DISCONNECTING MEANS. A NOTE WILL SUFFICE. | | | 3. PROVIDE A NOTE TO INDICATE SEPARATE PERMITS REQUIRED | | | FOR ANY LOW VOLTAGE SYSTEMS. | | | 4. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL | | | FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE | | | ANY QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | |
|