Plan Review Notes
Plan Review Notes For Permit 16030477
Permit Number 16030477
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-14 14:05:21REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - NEC 215.5 PROVIDE LOAD CALCULATIONS ALONG PANEL
 SCHEDULE TO SHOW BREAKER AND WIRE SIZE.
  
 - NEC 220.61 PROVIDE NUETRAL LOAD DEMANDS CLACS
 PERMITTING FOR FEEDER AND SERVICE REDUCTION.
  
 - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.
  
  