| Plan Review Notes For Permit 16030477 |
| Permit Number |
16030477 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-14 14:05:21 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | - NEC 215.5 PROVIDE LOAD CALCULATIONS ALONG PANEL | | | SCHEDULE TO SHOW BREAKER AND WIRE SIZE. | | | | | | - NEC 220.61 PROVIDE NUETRAL LOAD DEMANDS CLACS | | | PERMITTING FOR FEEDER AND SERVICE REDUCTION. | | | | | | - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE | | | INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE | | | INSTALLED. | | | | | | |
|