| Plan Review Notes For Permit 16030447 |
| Permit Number |
16030447 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-03-21 06:42:23 | 1) SUBMIT TWO COPIES OF THE COMPLETE TEST REPORT FOR | | | THE PROFLEX MAXXIM SIM-90 PRODUCT.FBC 107.2.1. THE | | | SUBMITTED SPECIFICATION SHEET NOTES THAT THE PRODUCT | | | WAS TESTED TO ASTM E492-90. THE STANDARD REFERENCED IN | | | THE 2014 FBC IS THE ASTM E 492-09. THE PRODUCT MUST | | | COMPLY WITH THE 2009 EDITION OF THE STANDARD. | | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLOOOR | | | FINISH PRODUCT TO BE INSTALLED.FBC 107.2.1. | | | 3) THE MANUFACTURER'S SPECIFICATION SHEET NOTES THAT IT | | | WAS TESTED TO ASTM E 90-02 FOR AIR-BORNE SOUND. THE | | | STANDARD REFERENCED IN THE 2014 FBC IS ASTM E 90-04. | | | THE PRODUCT MUST COMPLY WITH THE 2004 STANDARD. | | | 4) THE SPECIFICATION THAT WAS SUBMITTED NOTES THAT THE | | | ASTM E90, E989, & E492 TESTS WERE CONDUCTED ON AN 8" | | | CONCRETE SLAB WITH ACOUSTIC CEILING. THIS PRODUCT | | | CANNOT BE INSTALLED IN THIS BUILDING UNLESS THE | | | CONSTRUCTION MATCHES THAT OF THE TEST SPECIMEN. | | | 5) THE MANUFACTURER'S SPECIFICATIONS SHALL LIST THE | | | FLAME SPREAD INDEX AND THE CRITICAL RADIANT FLUX PER | | | THE 2014 FBC SEC.804.4.2. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|