2016-03-21 06:42:231) SUBMIT TWO COPIES OF THE COMPLETE TEST REPORT FOR
 THE PROFLEX MAXXIM SIM-90 PRODUCT.FBC 107.2.1. THE
 SUBMITTED SPECIFICATION SHEET NOTES THAT THE PRODUCT
 WAS TESTED TO ASTM E492-90. THE STANDARD REFERENCED IN
 THE 2014 FBC IS THE ASTM E 492-09. THE PRODUCT MUST
 COMPLY WITH THE 2009 EDITION OF THE STANDARD.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLOOOR
 FINISH PRODUCT TO BE INSTALLED.FBC 107.2.1.
 3) THE MANUFACTURER'S SPECIFICATION SHEET NOTES THAT IT
 WAS TESTED TO ASTM E 90-02 FOR AIR-BORNE SOUND. THE
 STANDARD REFERENCED IN THE 2014 FBC IS ASTM E 90-04.
 THE PRODUCT MUST COMPLY WITH THE 2004 STANDARD.
 4) THE SPECIFICATION THAT WAS SUBMITTED NOTES THAT THE
 ASTM E90, E989, & E492 TESTS WERE CONDUCTED ON AN 8"
 CONCRETE SLAB WITH ACOUSTIC CEILING. THIS PRODUCT
 CANNOT BE INSTALLED IN THIS BUILDING UNLESS THE
 CONSTRUCTION MATCHES THAT OF THE TEST SPECIMEN.
 5) THE MANUFACTURER'S SPECIFICATIONS SHALL LIST THE
 FLAME SPREAD INDEX AND THE CRITICAL RADIANT FLUX PER
 THE 2014 FBC SEC.804.4.2.
  