| 2016-03-21 16:51:05 | MECHANICAL PROVISOS: | | | 3/21/16 | | | | | | 1) SECTION 809.2 FBC-14 EXISTING BUILDING- ALTERED | | | EXISTING SYSTEMS: | | | IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL | | | VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR | | | EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER | | | MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR | | | AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION | | | AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF | | | VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY | | | PROCEDURE OF ASHRAE 62. | | | 2) C408.2.2 AIR DISTRIBUTION SYSTEM TESTING, ADJUSTING | | | AND BALANCING. | | | CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT A WRITTEN | | | BALANCE REPORT BE PROVIDED TO THE OWNER OR THE | | | DESIGNATED REPRESENTATIVE OF THE BUILDING OWNER FOR | | | HVAC SYSTEMS SERVING ZONES WITH A TOTAL CONDITIONED | | | AREA EXCEEDING 5000 SQUARE FEET (465 M2). AIR | | | DISTRIBUTION SYSTEMS SHALL BE TESTED, ADJUSTED, AND | | | BALANCED BY A LICENSED ENGINEER OR A COMPANY OR | | | INDIVIDUAL HOLDING A CURRENT CERTIFICATION FROM A | | | RECOGNIZED TESTING AND BALANCING AGENCY ORGANIZATION IN | | | ACCORDANCE WITH GENERALLY ACCEPTED ENGINEERING | | | STANDARDS. | | | |
|