| 2016-07-28 08:19:21 | 07/28/16 RECEIVED E-MAIL FROM DANIEL RUIZ WITH REVISED |
| | ENERGY CALCULATIONS FORM R402-2014. BELOW ARE THE |
| | COMMENTS TO THE ENERGY CALCULATIONS. REVISE ENERGY |
| | CALCULATIONS AND SUBMIT TWO COPIES. OTHER ITEMS NEED TO |
| | BE ADDRESSED OR BUILDING REVIEW MAY BE APPROVED WITH |
| | PROVISO. FEES MAY APPLY. OWNER TO ADVISE IF PROVISO |
| | OPTION IS DESIRED AFTER ENERGY CALCULATIONS AND IMPACT |
| | FEES ISSUES ARE ADDRESSED OR IF ADDRESSING ALL COMMENT |
| | PRIOR TO OBTAINING THE PERMIT. |
| | |
| | RESIDENTIAL (R3) ADDITION, FOURTH BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | ORIGINAL COMMENT: |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| | BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| | THE UNIFIED LAND DEVELOPMENT CODE. |
| | RESPONSE: |
| | NOT DONE YET. THIS MAY BE DONE WHEN PERMIT IS READY |
| | TO-BE ISSUED. |
| | |
| | ORIGINAL COMMENT: |
| | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: |
| | REVISE ENERGY CALCULATIONS SUBMITTED: (1) ITEM #1 IS |
| | NEW CONSTRUCTION, NOT YES. (2) ITEM #2 IS SINGLE FAMILY |
| | STORAGE, NOT NO.. (3) ITEM #4 IS NO, NOT N/A. (4) ITEM |
| | #12A IS ROOM AIR CONDITIONER, NOT AIR CONDITIONER. |
| | ALSO, REVISE THE TABLE R402A: (1)THERE IS NO FLOOR OVER |
| | UNCONDITIONED SPACE. THIS IS ONLY ONE FLOOR ON SLAB ON |
| | GRADE. THERE IS NO SPACE BELOW THE CONCRETE SLAB. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 3- PROVIDE ICC EVALUATION REPORT FOR THE TYPE OF SPRAY |
| | INSULATION TO BE INSTALLED SHOWING COMPLIANCE WITH SEC. |
| | R316 F FBC-RESIDENTIAL, 5TH EDITION (2014). (NOTE: |
| | ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING THE |
| | REPORT PRIOR TO SUBMITTAL TO THIS OFFICE). |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | ORIGINAL COMMENT: |
| | A) ENTRY DOOR AS SHOWN ON PLANS. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | B) WINDOWS AS SHOWN ON PLANS |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | NEW COMMENT: |
| | C) CEMENT BOARD AS SPECIFIED ON WALL SECTIONS. |
| | |
| | ORIGINAL COMMENT: |
| | 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |