| Date |
Text |
| 2016-07-27 08:55:23 | 07/26/16 RECEIVED E-MAIL FROM DANIEL RUIZ WITH ENERGY |
| | CALCULATIONS FORM R402-2014. BELOW ARE THE COMMENTS TO |
| | THE ENERGY CALCULATIONS. REVISE ENERGY CALCULATIONS AND |
| | SUBMIT TWO COPIES. OTHER ITEMS NEED TO BE ADDRESSED OR |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. FEES MAY |
| | APPLY. OWNER TO ADVISE IF PROVISO OPTION IS DESIRED |
| | AFTER ENERGY CALCULATIONS AND IMPACT FEES ISSUES ARE |
| | SUBMITTED OR IF ADDRESSING ALL COMMENT PRIOR TO |
| | OBTAINING THE PERMIT. |
| | |
| | RESIDENTIAL (R3) ADDITION, THIRD BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | ORIGINAL COMMENT: |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| | BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| | THE UNIFIED LAND DEVELOPMENT CODE. |
| | RESPONSE: |
| | NOT DONE YET. THIS MAY BE DONE WHEN PERMIT IS READY |
| | TO-BE ISSUED. |
| | |
| | ORIGINAL COMMENT: |
| | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: |
| | REVISE ENERGY CALCULATIONS SUBMITTED: (1) NEW |
| | CONSTRUCTION. (2) SINGLE FAMILY STORAGE. (3) NO WORST |
| | CASE. (4) PROVIDE TOTAL WINDOW AREA. (5) SLAB ON GRADE |
| | IS NR (NOT REQUIRED) NOT NA. (6) EXTERIOR ADJACENT WALL |
| | IS NA NOT R4 OR HIGHER. (7) COOLING TYPE ROOM AIR |
| | CONDITIONER NOT NA. ALSO, REVISE THE TABLE R402A: (1) |
| | THE EXTERIOR DOOR IS EXEMPT FROM THE U-FACTOR. SEE NOTE |
| | #3. (2) THERE IS NO FLOOR OVER UNCONDITIONED SPACE. (3) |
| | REVISE THE EER FACTOR OF THE ROOM UNIT TO MATCH VALUE |
| | GIVEN ON FRONT PAGE ITEM #12B. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 3- PROVIDE ICC EVALUATION REPORT FOR THE TYPE OF SPRAY |
| | INSULATION TO BE INSTALLED SHOWING COMPLIANCE WITH SEC. |
| | R316 F FBC-RESIDENTIAL, 5TH EDITION (2014). (NOTE: |
| | ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING THE |
| | REPORT PRIOR TO SUBMITTAL TO THIS OFFICE). |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | ORIGINAL COMMENT: |
| | A) ENTRY DOOR AS SHOWN ON PLANS. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | B) WINDOWS AS SHOWN ON PLANS |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | NEW COMMENT: |
| | C) CEMENT BOARD AS SPECIFIED ON WALL SECTIONS. |
| | |
| | ORIGINAL COMMENT: |
| | 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |