Date Text
2016-07-05 09:19:40** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SIGNED AND SEALED SURVEY OF THE PROPERTY IS MISSING
 FROM THE PERMIT SUBMITTAL. PLEASE PROVIDE AN UPDATED
 SURVEY OF THE PROPERTY. THE PHOTOCOPY PROVIDED IS
 INSUFFICIENT.
  
 2.) BUILDING PLANS ARE NOT MEASURABLE/NOT TO SCALE.
 (REFERENCE SHEET 4 OF 7, ELEVATIONS]
  
 3.) PROVIDE THE HEIGHT OF THE PROPOSED STRUCTURE IN THE
 PLANS. PLEASE NOTE THAT THE STRUCTURE MAY NOT EXCEED 25
 FT. IN HEIGHT. [ZLDR S.94-304(B)(4)]
  
 4.) IT IS UNCLEAR TO WHETHER OR NOT AN A/C UNIT IS
 PROPOSED FOR THE PROPOSED STORAGE UNIT. ILLUSTRATE THE
 LOCATION OF THE A/C UNIT AND SETBACKS FROM THE PROPERTY
 LINE IF AN A/C UNIT IS PROPOSED.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  
  
 NOTE:
  
 *PROPERTY IS ZONED SF7. PER THE SUBMITTED PERMIT PLANS,
 THE PROPOSED ACCESSORY STRUCTURE IS A STORAGE BUILDING;
 NO ACCESSORY DWELLING UNIT IS PERMITTED IN THE SF7
 ZONE.
  