| 2016-07-06 14:20:08 | RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | ORIGINAL COMMENT: |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| | BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| | THE UNIFIED LAND DEVELOPMENT CODE. |
| | RESPONSE: |
| | NOT DONE YET. THIS MAY BE DONE WHEN PERMIT IS READY |
| | TO-BE ISSUED. |
| | |
| | ORIGINAL COMMENT: |
| | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: |
| | REPEAT COMMENT. NOT DONE |
| | |
| | ORIGINAL COMMENT: |
| | 3 - PROVIDE ICC EVALUATION REPORT FOR THE TYPE OF SPRAY |
| | INSULATION TO BE INSTALLED SHOWING COMPLIANCE WITH SEC. |
| | R316 F FBC-RESIDENTIAL, 5TH EDITION (2014). (NOTE: |
| | ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING THE |
| | REPORT PRIOR TO SUBMITTAL TO THIS OFFICE). |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | ORIGINAL COMMENT: |
| | A) ENTRY DOOR AS SHOWN ON PLANS. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | B) WINDOWS AS SHOWN ON PLANS |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | NEW COMMENT: |
| | C) CEMENT BOARD AS SPECIFIED ON WALL SECTIONS. |
| | |
| | ORIGINAL COMMENT: |
| | 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |