| 2016-07-22 07:06:10 | 1ST REVIEW FBC-14 RESIDENTIAL, ENERGY CONSERVATION. | | | PERMIT #16030442 | | | 7/22/16 | | | | | | 1) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN LISTING | | | THE MAKE AND MODEL OF THE UNIT, HEATING AND COOLING | | | CAPACITIES, AND EFFICIENCY RATING. | | | | | | 2) PROVIDE AC COOLING AND HEATING CALCULATIONS IN | | | ACCORDANCE WITH SECTION R403.6.1 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 3) PROVIDE ENERGY CALCULATIONS FOR THE PROPOSED NEW | | | CONDITIONED BUILDING. PLEASE SEE SECTION R101.4.8: | | | ALTHOUGH THE BUILDING IS LABELED A STORAGE BUILDING, IT | | | IS NOT EXEMPT FROM MEETING COMPLLAINCE WITH THE CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|