| Plan Review Notes For Permit 16030442 |
| Permit Number |
16030442 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-15 14:37:11 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1.PLEASE CLARIFY THE RISER DIAGRAM SHOWN. PER NEC | | | 225.30 THIS OTHER STRUCTURE REQUIRES A PANEL BOARD DUE | | | TO MORE THAN 1 BRANCH CIRCUIT SHOWN. ALTHOUGH A PANEL | | | IS SHOWN ON NEW STRUCTURE THE RISER DIAGRAM DOES NOT | | | SHOW IT. PROVIDE THE PANEL SCHEDULE OF EXISTING | | | STRUCTURE TO SHOW BREAKER FEEDING NEW DETACHED | | | STRUCTURE PANEL | | | BOARD. OR CLARIFY INTENT. | | | 2.SHOW AN EXTERIOR WP GFCI PROTECTED RECEPTACLE OUTLET | | | ON NEW STRUCTURE. | | | 3.COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | | THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|