2016-03-15 14:37:11INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE CLARIFY THE RISER DIAGRAM SHOWN. PER NEC
 225.30 THIS OTHER STRUCTURE REQUIRES A PANEL BOARD DUE
 TO MORE THAN 1 BRANCH CIRCUIT SHOWN. ALTHOUGH A PANEL
 IS SHOWN ON NEW STRUCTURE THE RISER DIAGRAM DOES NOT
 SHOW IT. PROVIDE THE PANEL SCHEDULE OF EXISTING
 STRUCTURE TO SHOW BREAKER FEEDING NEW DETACHED
 STRUCTURE PANEL
 BOARD. OR CLARIFY INTENT.
 2.SHOW AN EXTERIOR WP GFCI PROTECTED RECEPTACLE OUTLET
 ON NEW STRUCTURE.
 3.COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  