Plan Review Notes
Plan Review Notes For Permit 16030442
Permit Number 16030442
Review Stop B
Sequence Number 1
Notes
Date Text
2016-04-12 09:45:04RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: FBC-5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 3- CLARIFY WHY THERE IS A BATHROOM AND ELECTRICAL
 CALCULATIONS FOR SMALL APPLIANCES, WATER HEATER AND AIR
 CONDITIONING FOR AN STORAGE BUILDING. ALSO, CLARIFY
 WHAT IS THE PURPOSE OF HAVING SO MANY OUTLETS FOR AN
 STORAGE BUILDING. CLEARLY IDENTIFY WHAT IS THE PROPOSED
 USE OF THIS BUILDING. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- SHEET 1 OF 7:
 A) PLANS NEED TO BE DRAWN TO SCALE. ENGINEERED PLANS
 SUBMITTED DON'T MATCH THE SCALE SHOWN ON PLANS (SCALE:
 1:40). REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) SPECIFY SPACING OF ALL FRAMING MEMBERS SHOWN ON THE
 FOUNDATION PLAN. SEC. 107.2.1 CITY AMENDMENTS.
  
 C) PROPOSED FOUNDATION SECTION A/1 TO SHOW COMPLIANCE
 WITH THE HEIGHT ABOVE FINISHED GRADE SEC. R404.1.6 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). (NOTE: COORDINATE
 WITH FOOTING SIZES SHOWN ON FOOTING SCHEDULE).
  
 D) PROPOSED FOUNDATION SECTION A/1 TO SHOW COMPLIANCE
 WITH THE MINIMUM FOOTING DEPTH AS REQUIRED BY SEC.
 R403.1.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014). (NOTE:
 COORDINATE WITH FOOTING SIZES SHOWN ON FOOTING
 SCHEDULE).
  
 E) PROPOSED FOUNDATION SECTION A/1 TO SHOW COMPLIANCE
 WITH THE 6" MINIMUM CLEARANCE BETWEEN EXTERIOR WALL
 COVERING AND FINAL GRADE AS REQUIRED BY SEC. R318.7 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). (NOTE: COORDINATE
 WITH FOOTING SIZES SHOWN ON FOOTING SCHEDULE).
  
 F) TYPICAL WINDOW FRAMING DETAIL AND TYP DOOR FRAMING
 DETAIL DON'T MATCH FRAMING SHOWN ON PLANS. SEE NUMBER
 AND TYPE OF STUDS SHOWN ON EACH END OF EACH OPENING.
 ALSO, SEE ROOF FRAMING PLAN FOR ORIENTATION OF ROOF
 JOISTS AND REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 G) TYPE OF CONNECTORS SHOWN ON TYPICAL WINDOW DETAIL
 AND TYPICAL DOOR DETAIL DON'T MATCH TYPE OF CONNECTOR
 SPECIFIED. FOR EXAMPLE: SIMPSON H3 CONNECTOR DOESN'T
 LOOK THE WAY IT'S SHOWN. IT LOOKS MORE LIKE A TYPE "U"
 CONNECTOR THAT IS TYPICALLY USED FOR BOTTOM AND TOP
 PLATES TO CONNECT TO THE WOOD STUDS. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 5-SHEET 2 OF 7:
 A) PLANS NEED TO BE DRAWN TO SCALE. ENGINEERED PLANS
 SUBMITTED DON'T MATCH THE SCALE SHOWN ON PLANS (SCALE:
 1:40). REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) PROPOSED ROOF SECTION A/2 SHOWS R-30 SPRAY
 INSULATION AND NEW 3" WIDE CONT. ALUM. AIR VENT. IT'S
 NOT CLEAR IF THE ROOF IS DESIGNED AS VENTED OR
 UNVENTED. SPRAY INSULATION IS TYPICALLY USED FOR
 UNVENTED ATTICS. BUT, DETAILS IS SHOWING VENTED SOFFIT
 AND SPRAY INSULATION. REVISE CLARIFY AS REQUIRED. SEE
 SEC. R806 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 C) PROPOSED ROOF SECTION A/2 SHOWS JOIST AT 12" O.C.
 THIS DOESN'T MATCH ROOF FRAMING PLAN. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 D) WALL SECTIONS NEED TO SPECIFY THE EXTERIOR FINISH.
 FOR EXAMPLE FOR STUCCO FINISH SEE TABLE R702.1(1) OF OF
 FBC-RESIDENTIAL, 5TH EDITION (2014) FOR REQUIRED
 THICKNESS. IF USING GYPSUM BOARD FOR INTERIOR FINISH,
 THEN SEE SEC. R702.3 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 6- SHEET 3 OF 7:
 A) SPECIFY THE CEILING HEIGHT ON NON-LOAD BEARING WALL
 B/3 TO VERIFY COMPLIANCE WITH SEC. R305 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) PLANS NEED TO BE DRAWN TO SCALE. ENGINEERED PLANS
 SUBMITTED DON'T MATCH THE SCALE SHOWN ON PLANS (SCALE:
 1:20). REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 7- PROVIDE ICC EVALUATION REPORT FOR THE TYPE OF SPRAY
 INSULATION TO BE INSTALLED SHOWING COMPLIANCE WITH SEC.
 R316 F FBC-RESIDENTIAL, 5TH EDITION (2014). (NOTE:
 ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING THE
 REPORT PRIOR TO SUBMITTAL TO THIS OFFICE).
  
 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ENTRY DOOR AS SHOWN ON PLANS.
  
 B) WINDOWS AS SHOWN ON PLANS
  
 C) HURRICANE SHUTTERS, IF WINDOWS AND DOOR WITH GLAZING
 DON'T HAVE IMPACT GLASS. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE.
  
 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- THE VALUATION DECLARED IN THE PERMIT APPLICATION IS
 TOO LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $11,642. ROBERT
 BROWN, THE BUILDING OFFICIAL, LOWERED THE PENALTY FOR
 BUILDING WITHOUT PERMIT TO 2X THE PERMIT FEE INSTEAD OF
 4X THE PERMIT FEE.
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]