| Plan Review Notes For Permit 16030431 |
| Permit Number |
16030431 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-21 10:43:12 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | - ELECTRIC RISER TO INCLUDE FEEDER/BRANCH CIRCUIT WIRE | | | SIZES AND CONDUIT DETAIL FROM ROOFTOP PANEL A TO AC | | | DISCONNECT WBA 107.3.5.3 | | | | | | - PROVIDE PANEL SCHEDULE WITH DEMAND LOADS ,AIC RATINGS | | | OF EQUIPMENT & OCPD TO VERIFY IF LOAD CAPACITY MATCHES | | | NAMEPLATE OF ROOFTOP CONDENSER UNIT. NEC 215.5 , | | | 110.9/10 , 440 | | | | | | - ELECTRICAL SUB-PERMIT IS REQUIRED PLEASE MAKE A NOTE | | | FOR ARC-FLASH HAZARD WARNING LABEL AND AVAILABLE FAULT | | | CURRENT MARKINGS. NEC 110.16 , 110.24 | | | | | | - ADJUSTMENT FACTORS WILL BE TAKEN INTO CONSIDERATION | | | FOR ALL RACEWAYS EXPOSED TO DIRECT SUNLIGHT ON TOP OF | | | ROOFTOPS ACCORDING TO NEC TABLE 310.15 B3. A NOTE WILL | | | SUFFICE. | | | | | | - PROVIDE A SERVICE RECEPTACLE GFCI PROTECTED WITHIN 25 | | | FT OR WITHIN SIGHT OF MECHANICAL EQUIPMENT. NEC 210.63 | | | , 210.8 B |
|