| 2016-03-26 05:07:00 | 1) PROVIDE SANITARY & WATER RISER DIAGRAMS FOR ALL | | | CHANGES TO THE PLUMBING SYSTEM.NOTE #5 ON SHT. M1 NOTES | | | THAT THE NEW SINK IS CONNECTING TO EXISTING SANITARY & | | | WATER LINES BUT AN EXISTING SINK IS NOT SHOWN ON | | | SHT.2.1. CLARIFY.FBC 107.3.5.1.3. | | | 2) THE WATER SUPPLY TO THE COFFEE MACHINES SHALL BE | | | PROTECTED AGAINST BACKFLOW PER 2014 FBC-PLUMBING | | | SEC.608.16.10. | | | 3) SUBMIT PIPING DETAILS FOR THE WATER HEATER AND PAN | | | DRAIN.WHAT TYPE OF FIXTURE IS THE PAN DRAIN DRAINING | | | TO? FBC 107.3.5.1.3. | | | 4) HOT WATER SHALL BE SUPPLIED TO THE BREAKROOM SINK | | | PER 2014 FBC-PLUMBING SEC.607.1. | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|