| Plan Review Notes For Permit 16030424 |
| Permit Number |
16030424 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-21 11:25:08 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16030424 | | | 3/21/16 | | | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW AHU'S #4 & 7- SEE SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION. | | | 2) SHEET M1: ALL CODE REQUIRED DUCT SMOKE DETECTORS | | | SHALL BE INSTALLED IN THE RETURN AIR SYSTEMS, PLEASE | | | REVISE NOTE #1 AND INDICATE IF ALL THE SYSTEMS WILL BE | | | LINKED TOGETHER FOR FAN SHUT IF ANY SINGLE DETECTOR | | | ACTIVATES. | | | 3) M1: THE 10" FLEX DUCTS SUPPLYING 350 AND 340 CFMS | | | FOR AHU-3 & 5 NEED TO INCREASE TO 12". | | | 4) M1: THE EXHAUST FROM EF-3 SHALL DISCHARGE TO THE | | | OUTDOORS IN ACCORDANCE WITH SECTION 501.3 FBC-14 | | | MECHANICAL. | | | 5) M1: NOTE #4: INDICATES THE NEW CU'S TO BE MOUNTED ON | | | EXISTING ROOF STANDS- PLEASE PROVIDE ENGINEERED DETAILS | | | FOR TIE DOWN OF THE UNITS- SECTION 301.15 FBC-14 | | | MECHANICAL. | | | 6) M2: PLEASE PROVIDE THE REQUIRED AND PROVIDED CFM'S | | | IN THE O/A CALCULATION TABLE. | | | 7) PROVIDE NOTE AND DETAILS INDICATING HOW ACCESS FOR | | | SERVICE AND REPLACEMENT OF THE ABOVE CEILING AHU'S AND | | | MOTORIZED DAMPERS WILL BE PROVIDED. | | | 8) M2: PROVIDE HANGING, REINFORCEMENT, AND CONNECTION | | | DETAILS FOR THE RIGID DUCTS IN ACCORDANCE WITH TABLE | | | C403.2.7.2 FBC-14 ENERGY CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|