2016-03-21 11:25:081ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030424
 3/21/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AHU'S #4 & 7- SEE SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
 2) SHEET M1: ALL CODE REQUIRED DUCT SMOKE DETECTORS
 SHALL BE INSTALLED IN THE RETURN AIR SYSTEMS, PLEASE
 REVISE NOTE #1 AND INDICATE IF ALL THE SYSTEMS WILL BE
 LINKED TOGETHER FOR FAN SHUT IF ANY SINGLE DETECTOR
 ACTIVATES.
 3) M1: THE 10" FLEX DUCTS SUPPLYING 350 AND 340 CFMS
 FOR AHU-3 & 5 NEED TO INCREASE TO 12".
 4) M1: THE EXHAUST FROM EF-3 SHALL DISCHARGE TO THE
 OUTDOORS IN ACCORDANCE WITH SECTION 501.3 FBC-14
 MECHANICAL.
 5) M1: NOTE #4: INDICATES THE NEW CU'S TO BE MOUNTED ON
 EXISTING ROOF STANDS- PLEASE PROVIDE ENGINEERED DETAILS
 FOR TIE DOWN OF THE UNITS- SECTION 301.15 FBC-14
 MECHANICAL.
 6) M2: PLEASE PROVIDE THE REQUIRED AND PROVIDED CFM'S
 IN THE O/A CALCULATION TABLE.
 7) PROVIDE NOTE AND DETAILS INDICATING HOW ACCESS FOR
 SERVICE AND REPLACEMENT OF THE ABOVE CEILING AHU'S AND
 MOTORIZED DAMPERS WILL BE PROVIDED.
 8) M2: PROVIDE HANGING, REINFORCEMENT, AND CONNECTION
 DETAILS FOR THE RIGID DUCTS IN ACCORDANCE WITH TABLE
 C403.2.7.2 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER