Plan Review Notes
Plan Review Notes For Permit 16030401
Permit Number 16030401
Review Stop Z
Sequence Number 2
Notes
Date Text
2016-04-12 13:44:59** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS IN WRITING OR ON
 THE PLANS WHERE APPLICABLE:
  
 1.) 3/18/16 REPEAT COMMENT: PROVIDE A SITE PLAN SHOWING
 THE SETBACK DISTANCE OF THE BUILDING FOOTPRINT TO THE
 PROPERTY LINES. PLEASE NOTE THAT THE SIDE SETBACKS
 SHALL BE A MINIMUM OF 5 FT. PER SIDE WITH A TOTAL SIDE
 SETBACK OF 15 FT. [ZLDR S.94-74(A)(3)]
  
 2.) 3/18/16 REPEAT COMMENT: LABEL ARCHITECTURAL PLANS
 WITH NORTH ARROW.
  
 3.) 3/18/16 REPEAT COMMENT: THE PROPOSED ARCHITECTURAL
 FLOOR PLANS SEEM TO INDICATE THE RELOCATION OF THE A/C
 UNIT TO THE EAST SIDE OF THE PROPERTY. IF THE A/C UNIT
 IS BEING RELOCATED TO A NEW LOCATION ON SITE, THEN THE
 SITE PLAN MUST ALSO DEMONSTRATE THAT THE A/C UNIT
 COMPLIES WITH THE SETBACK REQUIREMENTS FOR MECHANICAL
 EQUIPMENT.
  
 4.) 3/18/16 REPEAT COMMENT: THE A/C UNIT SHALL NOT
 PROJECT MORE THAN 4 FT. INTO A SETBACK. PLEASE SHOW
 COMPLIANCE IN THE SITE PLAN. [ZLDR S.94-305(B)(4)]
  
 REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.
  