| Plan Review Notes For Permit 16030401 |
| Permit Number |
16030401 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-22 08:56:49 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) TWO SETS OF HVAC EQUIPMENT SIZING CALCULATIONS WERE | | | SUBMITTED. THE PLANS INDICATE THAT ONE NEW DROP WILL BE | | | ADDED TO THE EXISTING DUCT SYSTEM. THERE ARE NOT ANY | | | NOTES ON THE PLANS INDICATING THE SIZE OF THE EXISTING | | | SYSTEM OR WHETHER OR NOT IT IS TO BE REPLACED. CLARIFY | | | THE INTENTION OF SUBMITTING THESE CALCULATIONS. | | | | | | 2) THE HVAC EQUIPMENT SIZING CALCULATIONS THAT WERE | | | SUBMITTED DO NOT LIST THE PROPOSED WOOD FRAME WALL. FBC | | | 107.2.1 | | | | | | 3) THE PROPOSED 2 X 6 WOOD FRAME WALL IS REQUIRED TO | | | HAVE A MINIMUM R-13 INSULATION VALUE PER FBC ENERGY | | | R402. THE WALL DETAIL ON SHEET 3 SPECIFIES R-11 | | | INSULATION. | | | | | | 4) SUBMIT TWO SETS OF ENERGY CODE COMPLIANCE | | | DEMONSTRATION FORMS REQUIRED BY FBC ENERGY R101.5.1. | | | FORMS ARE REQUIRED TO BE SIGNED AND DATED BY THE | | | PREPARER AND THE OWNER/AGENT. | | | |
|