2016-03-22 08:56:49PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) TWO SETS OF HVAC EQUIPMENT SIZING CALCULATIONS WERE
 SUBMITTED. THE PLANS INDICATE THAT ONE NEW DROP WILL BE
 ADDED TO THE EXISTING DUCT SYSTEM. THERE ARE NOT ANY
 NOTES ON THE PLANS INDICATING THE SIZE OF THE EXISTING
 SYSTEM OR WHETHER OR NOT IT IS TO BE REPLACED. CLARIFY
 THE INTENTION OF SUBMITTING THESE CALCULATIONS.
  
 2) THE HVAC EQUIPMENT SIZING CALCULATIONS THAT WERE
 SUBMITTED DO NOT LIST THE PROPOSED WOOD FRAME WALL. FBC
 107.2.1
  
 3) THE PROPOSED 2 X 6 WOOD FRAME WALL IS REQUIRED TO
 HAVE A MINIMUM R-13 INSULATION VALUE PER FBC ENERGY
 R402. THE WALL DETAIL ON SHEET 3 SPECIFIES R-11
 INSULATION.
  
 4) SUBMIT TWO SETS OF ENERGY CODE COMPLIANCE
 DEMONSTRATION FORMS REQUIRED BY FBC ENERGY R101.5.1.
 FORMS ARE REQUIRED TO BE SIGNED AND DATED BY THE
 PREPARER AND THE OWNER/AGENT.
  