| Plan Review Notes For Permit 16030381 |
| Permit Number |
16030381 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-15 14:56:45 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16030381 | | | 3/15/16 | | | | | | 1) PROVIDE AN EXHAUST VENTILATION CALCULATION FOR EF-1. | | | 2) PROVIDE THE WIND LOAD DESIGN CRITERIA AND | | | ENGINEERING FOR INSTALLATION OF THE ROOF MOUNTED FAN | | | AND CURB. PROVIDE A SECTION CUT INDICATING THE TYPE, | | | SIZE, AND AMOUNT OF FASTENERS FOR ANCHORING THE CURB TO | | | THE STRUCTURE, AND THE FAN TO THE CURB. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|