| 2016-04-06 10:09:43 | 1301 SUMMIT BOULEVARD |
| | PERMIT #16030381 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | UPDATE THE CODE LIST TO REFERENCE THE 2009 EDITION OF |
| | NFPA 150 - FIRE & LIFE SAFETY IN ANIMAL HOUSING |
| | FACILITIES |
| | |
| | SHEET A-001 INDICATES THE CONSTRUCTION TYPE TO BE TYPE |
| | VB. PER NFPA 150 - TABLE 7.2.2 ALL NON-SPRINKLERED |
| | BUILDINGS HOUSING CATERGORY B ANIMALS SHALL BE TYPE I |
| | OR TYPE II NON-COMBUSTIBLE CONSTRUCTION WHEN LOCATED |
| | ABOVE GRADE. |
| | |
| | SHEET A-001 ALSO INDICATES THAT OCELOTS ARE DEEMED TO |
| | BE A CATEGORY B IN LIEU OF A CATEGORY A. PLEASE DEFEND |
| | YOUR POSITION HOW A LARGE, FERAL FELINE SUBJECTED TO A |
| | STRENOUS EVENT SUCH AS A FIRE WOULD NOT POSE A DANGER |
| | TO HUMANS ATTEMPTING RESCUE. |
| | |
| | SECTION 6.3.1.1 CATEGORY A. CATEGORY A ANIMALS SHALL |
| | INCLUDE ANY OF THE FOLLOWING TYPES OF ANIMALS: |
| | (1) ANIMAL(S) THAT POSE A POTENTIAL RISK TO THE HEALTH |
| | OR SAFETY OF RESCUERS OR THE GENERAL PUBLIC |
| | (2) ANIMAL(S) THAT CANNOT BE REMOVED WITHOUT POTENTIAL |
| | RISK TO THE HEALTH AND WELFARE OF THE ANIMAL OR OTHER |
| | ANIMALS |
| | (3) ANIMAL(S) THAT ARE IMPOSSIBLE OR IMPRACTICAL TO |
| | MOVE |
| | CATEGORY B ANIMALS SHALL INCLUDE ALL ANIMALS NOT IN |
| | CATEGORY A. |
| | |
| | SHEET A-302: STAIR TREAD DEPTH IS ONLY 6-INCHES IN |
| | WIDTH AND NEEDS TO BE A MINIMUM OF 11-INCHES WIDE PER |
| | NFPA 101 - TABLE 7.2.2.2.1.1(A). |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |