| Plan Review Notes For Permit 16030375 |
| Permit Number |
16030375 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-10 19:16:17 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | - NEC 250.32 A BUILDINGS OR STRUCTURES SUPPLIED BY | | | FEEDERS OR BRANCH CIRCUITS SHALL HAVE A GROUNDING | | | ELECTRODE. | | | | | | - NEC 680.21 C GFCI PROTECTION REQUIRED FOR POOL | | | EQUIPMENT AND POOL PUMPS. ( NO POOL SPECS ON REAR LIKE | | | STATED ON REVISION APPLICATION. ) | | | | | | - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT, | | | SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET | | | SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE | | | SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE | | | LOCATED WITHIN 25 FT. OF THE EQUIPMENT. | | | | | | -FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | | FEET OF EACH SLEEPING ROOM. | | | | | | - NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES | | | | | | - NEC 110.26 HEIGHT OF WORKING CLEARNACE MAKE SURE | | | PANEL UNDER STAIRS MEETS 6FT REQUIREMENT. | | | | | | - NEC 210.70 LIGHTING OUTLET REQUIRED IN STAIRS ( 3 WAY | | | ) AND ALSO BASEMENT. | | 2016-03-10 09:27:18 | GAVE TO M. ALBARRAN |
|