Plan Review Notes
Plan Review Notes For Permit 16030369
Permit Number 16030369
Review Stop E
Sequence Number 2
Notes
Date Text
2016-07-27 08:47:35REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED AS A DEMOLITION PERMIT ONLY ALL TEMPORARY
 ELECTRIC SHALL BE GFCI PROTECTED IN ACCORDANCE WITH NEC
 590.6
  
 NEW PLANS TO INCLUDE THE FOLLOWING AS A MINIMUM :
  
 1) FBC 1006.1 ILLUMINATION REQUIRED.THE MEANS OF
 EGRESS, INCLUDING THE EXIT DISCHARGE, SHALL BE
 ILLUMINATED AT ALL TIMES THE BUILDING SPACE SERVED BY
 THE MEANS OF EGRESS IS OCCUPIED.
 - PLEASE SHOW EMERGENCY LIGHTING BY THE HALLWAYS TO
 VERIFY MINIMUM ILLUMINATION LEVELS OF 1 FOOT CANDLE AT
 THE WALKING SURFACE. FBC 1006.2
  
 2) FBC 1011.1 EXITS AND EXIT ACCESS DOORS SHALL BE
 MARKED BY AN APPROVED EXIT SIGN READILY VISIBLE FROM
 ANY DIRECTION OF EGRESS TRAVEL. THE PATH OF EGRESS
 TRAVEL TO EXITS AND WITHIN EXITS SHALL BE MARKED BY
 READILY VISIBLE EXIT SIGNS TO CLEARLY INDICATE THE
 DIRECTION OF EGRESS TRAVEL IN CASES WHERE THE EXIT OR
 THE PATH OF EGRESS TRAVEL IS NOT IMMEDIATELY VISIBLE TO
 THE OCCUPANTS.
 INTERVENING MEANS OF EGRESS DOORS WITHIN EXITS SHALL BE
 MARKED BY EXIT SIGNS. EXIT SIGN PLACEMENT SHALL BE SUCH
 THAT NO POINT IN AN EXIT ACCESS CORRIDOR OR EXIT
 PASSAGEWAY IS MORE THAN 100 FEET (30 480 MM) OR THE
 LISTED VIEWING DISTANCE FOR THE SIGN, WHICHEVER IS
 LESS, FROM THE NEAREST VISIBLE EXIT SIGN.
 - SHOW EXIT SIGNS LOCATION IN THE HALLWAYS TO COMPLY.
  
 3) ILLUMINATION SHALL BE PROVIDED FOR ALL WORKING
 SPACES ABOUT SERVICE EQUIPMENT, SWITCHBOARDS,
 PANELBOARDS. NEC 110.26(D) SHOW LIGHTING BY THE
 ELECTRICAL PANELS IN THE HALLWAYS TO COMPLY WITH THIS
 REQUIREMENT.
  