| 2016-07-27 08:47:35 | REVIEW 2014 5TH FBC ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | PASSED AS A DEMOLITION PERMIT ONLY ALL TEMPORARY |
| | ELECTRIC SHALL BE GFCI PROTECTED IN ACCORDANCE WITH NEC |
| | 590.6 |
| | |
| | NEW PLANS TO INCLUDE THE FOLLOWING AS A MINIMUM : |
| | |
| | 1) FBC 1006.1 ILLUMINATION REQUIRED.THE MEANS OF |
| | EGRESS, INCLUDING THE EXIT DISCHARGE, SHALL BE |
| | ILLUMINATED AT ALL TIMES THE BUILDING SPACE SERVED BY |
| | THE MEANS OF EGRESS IS OCCUPIED. |
| | - PLEASE SHOW EMERGENCY LIGHTING BY THE HALLWAYS TO |
| | VERIFY MINIMUM ILLUMINATION LEVELS OF 1 FOOT CANDLE AT |
| | THE WALKING SURFACE. FBC 1006.2 |
| | |
| | 2) FBC 1011.1 EXITS AND EXIT ACCESS DOORS SHALL BE |
| | MARKED BY AN APPROVED EXIT SIGN READILY VISIBLE FROM |
| | ANY DIRECTION OF EGRESS TRAVEL. THE PATH OF EGRESS |
| | TRAVEL TO EXITS AND WITHIN EXITS SHALL BE MARKED BY |
| | READILY VISIBLE EXIT SIGNS TO CLEARLY INDICATE THE |
| | DIRECTION OF EGRESS TRAVEL IN CASES WHERE THE EXIT OR |
| | THE PATH OF EGRESS TRAVEL IS NOT IMMEDIATELY VISIBLE TO |
| | THE OCCUPANTS. |
| | INTERVENING MEANS OF EGRESS DOORS WITHIN EXITS SHALL BE |
| | MARKED BY EXIT SIGNS. EXIT SIGN PLACEMENT SHALL BE SUCH |
| | THAT NO POINT IN AN EXIT ACCESS CORRIDOR OR EXIT |
| | PASSAGEWAY IS MORE THAN 100 FEET (30 480 MM) OR THE |
| | LISTED VIEWING DISTANCE FOR THE SIGN, WHICHEVER IS |
| | LESS, FROM THE NEAREST VISIBLE EXIT SIGN. |
| | - SHOW EXIT SIGNS LOCATION IN THE HALLWAYS TO COMPLY. |
| | |
| | 3) ILLUMINATION SHALL BE PROVIDED FOR ALL WORKING |
| | SPACES ABOUT SERVICE EQUIPMENT, SWITCHBOARDS, |
| | PANELBOARDS. NEC 110.26(D) SHOW LIGHTING BY THE |
| | ELECTRICAL PANELS IN THE HALLWAYS TO COMPLY WITH THIS |
| | REQUIREMENT. |
| | |