| 2016-06-15 14:02:48 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER ? PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | DATE: 6/15/16 |
| | ACTION: FAIL |
| | |
| | THE PLANS RE-SUBMITTED FOR REVIEW CONSIST OF A |
| | RE-DESIGN FROM THE 1ST REVIEW. THE ARCHITECTURAL AND |
| | LIFE SAFETY PLANS SUBMITTED ARE LIMITED IN SCOPE AND |
| | GENERAL IN NATURE. A THOROUGH REVIEW CANNOT BE |
| | PERFORMED AT THIS TIME. THE ATTACHED LIST OF ITEMS IS |
| | FOR GUIDANCE ONLY AND IS NOT TO BE CONSTRUED AS A FINAL |
| | LIST OF COMMENTS TO BE ADDRESSED BY THE DESIGN TEAM. |
| | ADDITIONAL COMMENTS MAY BE GENERATED UPON RE-SUBMITTAL |
| | OF PLANS. |
| | |
| | 1. PROVIDE DETAIL OF NEW ISOLATED SPREAD FOOTINGS. |
| | 2. PROVIDE DETAIL & SHOP DRAWINGS OF NEW STRUCTURAL |
| | STEEL SKELETON STRUCTURE. |
| | 3. PROVIDE SHOP DRAWINGS OF NEW STAIRS (BY OTHERS). |
| | 4. PROVIDE SHORING PLAN FOR REMOVAL OF STRUCTURAL |
| | SLABS. |
| | 5. PROVIDE DETAIL OF EXISTING WALLS TO BE USED AS PART |
| | OF RATED SHAFT. WALLS SHALL COMPLY WITH FBC 706 (WALLS) |
| | AND 713 (SHAFTS). |
| | 6. PROVIDE DETAIL OF NEW WALLS TO BE USED AS PART OF |
| | RATED SHAFT. WALLS SHALL COMPLY WITH UL 404 PER PLANS. |
| | 7. PROVIDE DETAIL OF RATED DOOR ASSEMBLY. DOORS SHALL |
| | BE RATED PER FBC TABLE 716.5 AND INSTALLED PER NFPA 80. |
| | 8. PROVIDE EXIT DOOR HARDWARE SPECS. |
| | 9. PROVIDE STAIRWAY ILLUMINATION PER FBC 1011.3. |
| | 10. LABEL STAIRS ACCORDING TO THE JEZERINAC GROUP'S |
| | REPORT. STAIR # 1 AND STAIR #2. LOBBY STAIRS ARE |
| | EXISTING AND ARE OUTSIDE THE SCOPE OF THIS SUBMITTAL. |
| | 11. PROVIDE LIFE SAFETY PLAN INDICATING PATH OF TRAVEL |
| | AND EXIT DISCHARGE TO A PUBLIC WAY, DISTANCE TO EXIT'S, |
| | EMERGENCY ILLUMINATION AND RATED WALLS. |
| | 12. VALUE OF PROJECT APPEARS LOW. |
| | 13. MECHANICAL, ELECTRICAL & PLUMBING PERMITS REQUIRED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY |
| | DELAY THE APPLICATION PROCESS. |
| | |
| | |