| 2016-06-15 15:30:48 | REVIEW 2014 5TH FBC ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |
| | -THE FOLLOWING ARE THE ELECTRICAL REQUIREMENTS THAT |
| | APPLY TO THE INTERIOR STAIRWAY MEANS OF EGRESS |
| | |
| | - 1006.1 ILLUMINATION REQUIRED. 1006.2 ILLUMINATION |
| | LEVEL. |
| | THE MEANS OF EGRESS, INCLUDING THE EXIT DISCHARGE, |
| | SHALL BE ILLUMINATED AT ALL TIMES THE BUILDING SPACE |
| | SERVED BY THE MEANS OF EGRESS IS OCCUPIED. |
| | THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE |
| | LESS THAN 1 FOOTCANDLE (11 LUX) AT THE WALKING SURFACE. |
| | |
| | - FBC-B 1011. EXIT SIGNAGE REQUIRED.THE FACE OF AN EXIT |
| | SIGN ILLUMINATED FROM AN EXTERNAL SOURCE SHALL HAVE AN |
| | INTENSITY OF NOT LESS THAN 5 FOOTCANDLES |
| | |
| | - NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL BE |
| | FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR |
| | MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY |
| | BE ON OWN CIRCUIT. |
| | |
| | - 1022.5 PENETRATIONS. |
| | PENETRATIONS INTO AND OPENINGS THROUGH INTERIOR EXIT |
| | STAIRWAYS AND RAMPSARE PROHIBITED EXCEPT FOR REQUIRED |
| | EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR |
| | INDEPENDENT VENTILATION OR PRESSURIZATION, SPRINKLER |
| | PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR FIRE |
| | DEPARTMENT COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY |
| | SERVING THE INTERIOR EXIT STAIRWAY AND RAMP AND |
| | TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE |
| | INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE PROTECTED |
| | IN ACCORDANCE WITH SECTION 714. THERE SHALL BE NO |
| | PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER |
| | PROTECTED OR NOT, BETWEEN ADJACENT INTERIOR EXIT |
| | STAIRWAYS AND RAMPS. OPEN PENETRATIONS SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 714.3.2. |
| | |
| | |