2016-03-11 13:41:38THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. THE SUBMITTED PLAN INDICATE THE COVERING
 OVER/THROUGH AN EXIT PATH OF TRAVEL. THERE IS NO
 INDICATION OF EXIT PATH ILLUMINATION PER NFPA 101,
 CHAPTER 7, MEANS OF EGRESS.
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
  
 7.8.1 GENERAL.
  
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11
 THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
  
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE
 MEANS OF EGRESS BE AVAILABLE FOR USE, UNLESS OTHERWISE
 PROVIDED IN 7.8.1.2.2.
  
 PLEASE PROVIDE THE CONTINUATION OF THE EXISTING AND
 REQUIRED LIGHTING OF PATH OF TRAVEL.
  
  