Plan Review Notes
Plan Review Notes For Permit 16030364
Permit Number 16030364
Review Stop B
Sequence Number 1
Notes
Date Text
2016-03-09 10:54:33****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. BASED ON THE SITE PLAN PROVIDED, IT APPEARS THAT THE
 PEDESTRIAN PROTECTION WILL ENCROACH THE PROPERTY LINE.
 PROVIDE A LETTER GRANTING PERMISSION FROM THE ADJACENT
 PROPERTY OWNER.
  
 2. THE PLANS PROVIDED LACK A TITLE BLOCK FOR THE
 ENGINEER, FS 471, FAC61G15-23.002. THE PLANS ALSO DO
 NOT CORRECTLY IDENTIFY THE PROJECT (FORT LAUDERDALE IS
 SHOWN AS THE LOCATION).
  
 3. THE PLAN SUBMITTED REQUIRES THAT THE STRUCTURAL
 ENGINEER CONFIRM THAT THE STRUCTURE THAT THE SCAFFOD
 SYSTEM IS RESTING ON IS CAPABLE OF SUPPORTING THE
 SUPERIMPOSED LEG LOAD OF 6300 LBS. A SHOP DRAWING
 REVIEW STAMP OR REVIEW LETTER IS REQUIRED.
  