| Plan Review Notes For Permit 16030363 |
| Permit Number |
16030363 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-15 11:07:25 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16060363 | | | 3/15/16 | | | | | | 1) PLEASE CLARIFY HOW AIR FORM OFFICE 103 & 104 IS | | | BEING RETURNED TO AHU-6. | | | 2) THE TRANSFER DUCTS FROM OFFICES 106, 107, 116, 120, | | | 121, 123, & 124 ARE UNDERSIZED PER SECTION 601.5 FBC-14 | | | MECHANICAL: TRANSFERS MUST BE SIZED 1.5 TIMES THE | | | CROSS-SECTIONAL AREA OF THE SUPPLY DUCT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|