| 2016-03-14 07:54:55 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE CLARIFY THE RISER DIAGRAM SHOWS SERVICE | | | CONDUCTORS ROUTED TO FPL TRANSFORMER AND NOT TAPED IN | | | EXISTING GUTTER. IF THE TAP OCCURS IN THE GUTTER PLEASE | | | SHOW AS SUCH AND DELETE ONE LINE STRAIGHT TO | | | TRANSFORMER. FBC 107.3.5 | | | 2. ADD A NOTE TO RISER DIAGRAM TO INDICATE NEC 110.16 | | | ARC-FLASH WARNING LABELS REQUIRED AND NEC 110.24 | | | REQUIREMENTS AVAILABLE FAULT CURRENTS. A NOTE WILL | | | SUFFICE. | | | 3. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL | | | FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE | | | ANY QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | |
|